SERVICING
Check the temperature setting and the anti-scalding safety at least twice a year (depending on the water
quality).
To ensure continued reliability of the PREMIX, and to conform with local Anti-Legionella legislation,
we recommend checking the following at least twice a year:
• Non-return valves, filters and replaceable cartridge: de-scale or replace worn or damaged parts.
• Mixing chamber: de-scale.
If the PREMIX is not mixing correctly (fig. D):
• Balance the pressure. The pressure differential between the hot water and the cold water must be less
than 1 bar.
• Check the hot water supply temperature. The temperature should be higher than 55°C.
• Shut off the water supply.
• Check that the filters have been installed correctly. Replace if necessary.
• Check the non-return valves . Replace if necessary.
• To remove the mechanism:
- Unscrew the outlet nipple using a 35mm spanner.
- Remove the spring .
- Remove the thermostatic element and the shuttle by hand.
• Clean the thermostatic element and the shuttle .
• Clean the mixer body interior.
• Replace the mechanism. Turn on the water supply. Always carry out a cold water failsafe check after
dismantling or carrying out maintenance.
MAINTENANCE & CLEANING
• Cleaning chrome, aluminium and stainless steel: do not use abrasive, chlorine or any other
acid-based cleaning products. Clean with mild soapy water using a cloth or a sponge.
• Frost protection: drain the pipes and operate the mixer/tap/valve several times to drain any
remaining water. In the event of prolonged exposure to frost, we recommend taking the mechanisms
apart and storing them indoors.
After Sales Care Support:
The installation guide is available on: www.delabie.co.uk
The installation guide is available on: www.delabie.com
EN