en
Description and function
PWM 1 signal input (%)
93 ... 100
PWM 2 mode (profile solar)
In PWM 2 mode, the pump speed is controlled depending on the PWM input signal.
Behaviour when a cable breaks:
If the signal cable is disconnected from the pump, e.g. due to a cable break, the pump
stops.
PWM 2 signal input (%)
< 7
7 ... 15 (operation)
12 ... 15 (starting)
15 ... 95
> 95
PWM signal output (iPWM)
In iPWM mode, the pump produces a PWM output signal. In normal operation, either
the volume flow or the power is calculated. In case of a failure, a specific code is
transmitted.
PWM signal output (%)
2
5 ... 75
72
Pump reaction
Pump stops (standby).
n/¹/min
max
min
0
7 12 15
Pump reaction
Pump stops (standby).
Pump runs at minimum speed.
Pump runs at minimum speed.
The speed of the pump increases linearly from n
Pump runs at maximum speed.
Volume flow calculation
Pump stopped by user instruction, ready to start.
The volume flow of the pump in-
creases linearly from 0 ... Q
95 100
min
Power calculation
The power consumption of the
(m³/h).
pump increases linearly from
max
5 ... P1
(W).
max
PWM %
to n
.
max
WILO SE 2022-04
Tabla de contenido
loading