Maintenance; Cleaning; Troubleshooting - Daikin FWTOUCH Manual De Instalacion Y Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

10.7 MAINTENANCE

IMPORTANT:
Maintenance operations must
be carried out only by a service centre au-
thorised by the manufacturer or by qualified
personnel. For safety reasons, before per-
forming any maintenance or cleaning opera-
tions, switch off the unit.

Cleaning

If it is necessary to clean the control panel (user

10.8 TROUBLESHOOTING

If the unit to which the FWTOUCH controller is
connected is not working properly, before re-
questing service, perform the checks indicated
in the table in the unit's installation, use, and
maintenance manual. If the problem cannot be
PROBLEM
The control panel does not turn on
The control panel displays a probe alarm
Incorrect reading of water temperature
Incorrect reading of air temperature on the control panel
Absence of communication with the monitoring system
Absence of communication with the MASTER in a SMALL network on
RS485
interface):
Ū use a soft cloth;
Ū never pour liquids onto the unit, as this could
cause electrical discharges and damage the
internal components;
Ū never use harsh chemical solvents;
Ū do not introduce metal parts through the
grille of the user interface's plastic casing.
solved, contact the dealer or service centre.
INFO:
For further information on mainte-
nance, cleaning, and troubleshooting, refer
to the manual of the unit on which the con-
troller is installed.
SOLUTION
Check the correct connection to the on-board circuit board (wiring and
polarity)
Check the power supply of the circuit board (STATUS LED on)
Replace the connection cable to the circuit board
Check that the circuit board is wired correctly
Verify the correct positioning of the probe inside the traps
Check that the airflow through the control panel is not blocked
Check that the control panel is not affected by external heat sources
Adjust the air probe offset parameter to calibrate the probe
Check that the RS485 line is wired correctly
Check the correct parameter configuration of the SLAVE controller
Check the correct setting of the communication parameters on the mon-
itoring system
Check that the PLC line is wired correctly
Check the correct parameter configuration of all network controllers
25
FC66006287
Tabla de contenido

Solución de problemas

loading

Tabla de contenido