Optional Settings - Johnson Controls PG9350SL Manual Del Usuario

Detector de haz fotoeléctrico inalámbrico
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Optional settings

Warning:
We do not recommend changing the default settings. Changing the default settings can cause the device to
function incorrectly and increases the chance of failure or false alarms.
DIP Switch and Output settings
Adjusting the beam interruption time
You can adjust the beam interruption time settings according for the detectors intended target using one of the four
selector positions below. The default setting is 50 ms.
D.Q. output (environmental disqualification)
The D.Q. output feature detects when the beam strength is below acceptable levels due to environmental factors such
as heavy rain, snow, or fog. If the beam strength is low for more than 20 seconds due to these conditions, a D.Q.
output signal is generated. The signal will return to normal when the beam strength is at acceptable levels for more
than 2 seconds.
Note: D.Q output is not evaluated by UL
The D.Q. output signal can be configured for one of the following uses:
Separate Output: Alerts the user that the detector is not working effectively due to weather conditions.
Bypass Alarm: Bypasses the alarm when the D.Q. output is triggered by adverse weather conditions.
You can configure either option with the following jumper pin settings on interface board of the Receiver:
D.Q. and Alarm Separate Output
Bypass Alarm Setting
Tabla de contenido
loading

Tabla de contenido