07: Modo bypass habilitado/deshabilitado cuando se apaga el UPS
Interfaz
08:
Bypass voltage range setting
Interfaz
09:
Bypass frequency range setting
Interfaz
Configuración
ENA: Modo Bypass activado cuando se apaga el UPS
DIS: Modo Bypass desactivado cuando se apaga el UPS
(Default)
Configuración
Parameter 1 & 2: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: setting the high voltage point in parameter 3 from
120Vac to 140Vac(Default: 132Vac)
LS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from
85Vac to 115Vac. (Default: 85Vac)
Configuración
Parameter 1 & 2:Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing the
Down key or Up key.
HS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz to
55HZ (Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz to
65Hz (Default: 63.0Hz)
LS: Bypass low Frequency point
For 50Hz output frequency models:
16