Installation Requirements - European Safety Systems BE S120D Serie Manual De Instrucciones

Sondas acústicas antideflagrantes
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23
2) Marking
All units have a rating label, which carries the following
important information:-
BExS120D or BExS110D
Unit Type No.
Input Voltage: DC Units
12V or 24V or 48V
AC Units
230V or 110V or 115V
Ex d IIC T4 for Ta –50°C to +55°C
Codes:
Ex d IIB T4 for Ta –50°C to +70°C
KEMA 99ATEX6312
Certificate No's
IECEx KEM 10.0003
Epsilon x:
Equipment Group
and Category:
CE Marking:
Notified Body No.
"Warnings"
DO NOT OPEN WHEN AN EXPLOSIVE
GAS ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC

4) Installation Requirements

Sounders must be installed in accordance with the following
or equivalent standards.
EN60079-14:2008
Electrical Installations in Hazardous
IEC60079-14:2007 (Ed4)
Areas (other than mines)
EN60079-10:2003
Classification of Hazardous Areas
IEC60079-10:2008 (Ed1)
Installation should only be carried by competent personnel
and any local codes of practice applied.
5) Zones, Gas Group, Category and Temperature
Classification
The units can be installed in locations with the following
conditions:-
Area Classification:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
www.acornfiresecurity.com
INSTRUCTION MANUAL (ATEX / IECEx)
BExS120D and BExS110D
II 2G
0518
www.acornfiresecurity.com
Flameproof Sounders
Gas Groupings:
Group IIA
Group IIB
Group IIC (Up to +55ºC only)
Equipment Category:
2G
Temperature Classification:
T1
400
T2
300
T3
200
T4
135
Ambient Temperature Range:
-50°C to +55°C Gas Groups IIA, IIB and IIC
-50°C to +70°C Gas Group IIA and IIB
6) Sounder Location and Mounting
See drawing A
7) Safety Warning (Electrostatic Hazard)
The acoustic horn section is made of ABS Plastic; therefore
to avoid a possible ELECTROSTACTIC CHARGE the unit
must only be cleaned with a damp cloth.
8) Access to the Flameproof Enclosure
See drawing B
Note the four M6 screws are Class A4-80 stainless steel
and only screws of this category can be used on these
sounders. It is therefore important that these screws and
their spring washers are kept in a safe place during
installation.
9) Power Supply Selection
The system power supply must have the necessary capacity
to provide the input current to all of the sounders connected
to the system.
The following table shows the input current taken by the
various sounder units:-
Unit Type
Input
Voltage
BExS120D
24V DC
BExS120D
12V DC
BExS120D
48V DC
BExS120D
230V AC
BExS120D
110V AC
BExS120D
115V AC
(GBR)
Propane
Ethylene
Hydrogen and Acetylene
o
C
o
C
o
C
o
C
Input
Max.
Current
I/P Volts
800mA
30V
850mA
15V
420mA
58V
90mA
264V
200mA
121V
180mA
126V