LEGRAND Wattstopper FSP-211B Instrucciones De Instalación
LEGRAND Wattstopper FSP-211B Instrucciones De Instalación

LEGRAND Wattstopper FSP-211B Instrucciones De Instalación

Alto/bajo/apagado, sensor exterior integrado del aplique pir en gabinete ip66
Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 22834 – 5/19 rev. 7
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: FSP-211B, FSP-211B-S, FSP-211B-D
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
The FSP-211B is an IP66 rated motion sensor that dims lighting from
high to low based on movement.
Three configurations are available. The FSP-211B mounts inside the
fixture and the PIR lens connects to the FSP-211B through a 1.30"
diameter hole in the bottom of the fixture. The FSP-211B-S mounts to
a fixture/enclosure with a 1/2" knock out, via a nipple on the back. The
FSP-211B-D has a drop mount nipple, for mounting on to a pole, or to
a fixture.
The sensor uses passive infrared (PIR) sensing technology that reacts to
changes in infrared energy (moving body heat) within the coverage area.
Once the sensor stops detecting movement and the time delay elapses,
lights will go from high to low mode and eventually to an OFF position if
it is desired. Sensors must directly "see" motion of a person or moving
object to detect them, so careful consideration must be given to sensor
luminaire placement and lens selection. Avoid placing the sensor where obstructions may block the sensor's line of sight.
The FSP-211B operates single phase at 120V/230V/240V/277V. No power pack is required. It is designed to be installed in indoor and
outdoor environments.
NOTE: When the FSP-211B is powered up the first time, it will use factory default parameters to operate. If adjustments are needed,
the FSIR-100 configuration tool must be used.
SPECIFICATIONS
Voltage .............................................120V/277V, 50/60Hz
............................230–240V, 50/60Hz, Single Phase
Load Ratings
@ 230–240V ........... 0 – 300W Ballast or LED Driver
@ 120V ...0–800W Tungsten, Ballasts or LED Driver
@ 277V ................. 0 – 1200W Ballast or LED Driver
Motor @ 120V/277V........................................1/6 HP
Wiring .................................................................... 18AWG
Length .......36" (91.44cm), 30" (76.2cm) from nipple
Line Voltage ................................ Line, Neutral, Load
Low Voltage ..................... Dim + (violet), Dim - (gray)
Operating Temperature ......-40°F (-40°C) to 167°F (75°C)
Tightening Skirt/Nut Torque ............................ 25–30 in-lbs
Dimensions
Collar ..................................1.30" diameter (33.0mm)
Collar height ......................................0.64" (16.3mm)
Body .. 5.7"L x 2.3"W x 3.5"H (145mm x 60mm x 90mm)
Weight ........................................................... 2.8 oz (80 g)
Enclosure ............................................. IP66 (NEMA STD)
Coverage
FSP-L2 Lens @ 8' height ..............up to 44' diameter
FSP-L3 Lens @ 20' height ............up to 40' diameter
FSP-L7 Lens @ 40' height ..........up to 100' diameter
Regulatory
Operating Control ............................................Type 1
Pollution Degree .......................................................2
Software .........................................................Class A
Impulse Voltage Rating ....................................... 4kV
Independently mounted for nipple or through hole
DESCRIPTION AND OPERATION
Wattstopper
High/Low/Off, PIR Fixture Integrated Outdoor Sensor In IP66 Enclosure
Haut/Bas/Éteint, Luminaire avec capteur IRP extérieur intégré dans un boitier IP66
Alto/Bajo/Apagado, Sensor exterior integrado del aplique PIR en gabinete IP66
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Sensor Protection Cap
NOTE: Remove Cap before use
®
Adjustments and Features
High Mode ..................................................0 V –10 V
Low Mode ................................. . . . . 0 V – 9.8 V, Off
Time Delay .................... 30 seconds, 1 min – 30 min
Cut Off ............... Disable, 1 min – 59 min ,1 hr – 5 hr
Sensitivity .................On-Fix, Off-Fix, Low, Med, Max
Hold Off Setpoint ......................Auto, None, 1–250 fc
Ramp Up .............................. Disable, 1 sec – 60 sec
Fade Down ........................... Disable, 1 sec – 60 sec
Photocell Setpoint for On/Off .......................1–250 fc
Factory Defaults
High Mode .......................................................... 10 V
Low Mode ................................................... . . . . 1 V
Time Delay ........................................................5 min
Cut Off ................................................................. 1 hr
Sensitivity ...........................................................Max
Hold Off Setpoint ...........................................Disable
Ramp Up ........................................................Disable
Fade Down .....................................................Disable
Photocell Setpoint for On/Off .........................Disable
PIR Sensor
Motion Indicator
Red LED
Light Sensor
IR Transmitter
IR Receiver
loading

Resumen de contenidos para LEGRAND Wattstopper FSP-211B

  • Página 11 INSTRUCCIONES EN ESPAÑOL ESPECIFICACIONES Voltaje ..............120V/277VCA, 50/60Hz Ajustes y funciones .............. 230–240VCA, fase simple Modo alto ................0 V a 10 V Especificaciones de carga Modo bajo ............0 V a 9,8 V, Apagado @ 230–240 V ....... Balasto o controlador LED de 0–300 W Tiempo de demora ....30 segundos, 1 minuto a 30 minutos @ 120 V ....
  • Página 12 INSTALACIÓN PRECAUCIÓN ADVERTENCIA: APAGUE LA WATTSTOPPER RECOMIENDA AGREGAR CORRIENTE EN EL DISYUNTOR UN SUPRESOR DE SOBRETENSIONES DE 20 ANTES DE INSTALAR EL SENSOR. KA PARA PROTEGER EL DISPOSITIVO, EL CONTROLADOR Y EL SENSOR DE FSP. Existen tres configuraciones del sensor: •...
  • Página 13 CABLEADO Controlador Controlador Neutro Neutro No-Atenuable Atenuable (Blanco) (Blanco) Carga Carga (Rojo) (Rojo) Violeta Atenuar (+) Violeta Atenuar (-) Gris Gris Neutro Neutro Línea (Negro) Línea (Negro) CONFIGURACIÓN DEL FSP-211B El proceso de configuración establece los parámetros adecuados para el funcionamiento del FSP-211B. Esto se realiza mediante la herramienta de configuración FSIR-100 Si no se realizan pasos de configuración, el sensor usará...
  • Página 14 COMUNICACIÓN IR La comunicación infrarroja puede verse afectada por la altura de montaje del sensor y la iluminación ambiental alta proveniente de luz de día directa o luz eléctrica, como ser reflectores y algunas lámparas halógenas, fluorescentes o LED. Al intentar comunicarse con el FSP-211B, asegúrese de ubicarse debajo del sensor sin ninguna obstrucción.
  • Página 15 INFORMACIÓN PARA HACER PEDIDOS N.º de catálogo Descripción FSP-211B Fase simple/doble (universal), sensor integrado de aplique PIR en gabinete IP66 FSP-211B-S Fase simple/doble (universal), sensor integrado de aplique PIR en gabinete IP66 con montaje de boquilla recta FSP-211B-D Fase simple/doble (universal), sensor integrado de aplique PIR en gabinete IP66 con montaje de boquilla de caída FSIR-100 Herramienta de configuración FSP-L2...