Figure 2 — An Alternate Transfer Switch Mounting
— — — — — — Control Wiring
Hot
Water
Heater

Power Wiring Interconnections

All wiring must be the proper size, properly supported and
protected by conduit.
Complete the following connections between the transfer
switch, main distribution panel, utility power and generator
(Figure 3, on next page).
Low voltage wire cannot be installed in same
conduit as power voltage wiring.
• Failure to follow above warning could cause personal injury,
damage and/or malfunction of equipment.
1.
Ensure utility power is turned OFF. Connect utility
service conductors to transfer switch terminals
marked "UTILITY CONNECTION".
2.
Connect utility neutral to the transfer switch
"NEUTRAL" terminal.
3.
Connect main distribution panel power leads to transfer
switch terminals marked "LOAD CONNECTION".
4.
Connect main distribution panel neutral lead to
transfer switch "NEUTRAL" terminal.
5.
Connect generator power supply leads from the
generator's control panel to transfer switch terminals
marked "GENERATOR CONNECTION".
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Operator's Manual
Contactor
Emergency
Load Center
Branch Circuits
WARNING
www.mymowerparts.com
Transfer
Main
Switch
Breaker
Panel
Disconnect Switch
Air
Conditioner
6.
Connect generator Neutral from the control panel to
the transfer switch "NEUTRAL" terminal.
7.
Connect generator "GND" from the control panel to
the transfer switch "GND" terminal.
8.
Connect main distribution panel "GND" to the
transfer switch "GND" terminal.
NOTE: Assure grounding electrode conductor is
connected and bonded per applicable federal, state and
local codes, standards and regulations.
9.
Connect generator utility 240 VAC terminals to
transfer switch utility 240 VAC terminals.
10. Tighten all wire connections/fasteners to proper
torque. See inside transfer switch enclosure for proper
torque values.

Supervisory Control Wiring

Terminal strip on control module in transfer switch has
four connections for customer use.There are two sets of
"Normally Closed" contacts available.They will be opened
when generator power is required.These can be used to
lock out large loads when powered by generator. Example:
air conditioner, hot water heater, etc..
7
Watt -
Hourmeter
Generator