Pressure Reducing Valve; Troubleshooting - Honeywell D15S Instrucciones De Montaje

Ocultar thumbs Ver también para D15S:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 18
8. Start-up
8.1. Setting outlet pressure
Set outlet pressure 1 bar minimum under inlet
pressure.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen hexagon nut on spring bonnet
5. Slacken tension in compression spring
6. Slowly open shutoff valve on inlet
7. Rotate adjustment screw, until the pressure gauge shows
the desired value
8. Retighten hexagon nut
9. Slowly open shutoff valve on outlet
9. Maintenance
We recommend a planned maintenance contract with
an installation company
In accordance with DIN EN806-5, the following measures
must be taken:
9.1. Inspection

9.1.1. Pressure reducing valve

Interval: once a year
1. Close shutoff valve on outlet
2. Check outlet pressure using a pressure meter when there
is zero through-flow
• If the pressure is increasing slowly, the valve may be
dirty or defective. In this instance, carry out servicing
and cleaning
3. Slowly open shutoff valve on outlet

11. Troubleshooting

Problem
Water is escaping from the spring
bonnet
Too little or no water pressure
Honeywell GmbH
GB
9.2. Maintenance
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen hexagon nut on spring bonnet
5. Slacken tension in compression spring
6. Unscrew spring bonnet
7. Check the cartridge insert for fault-free condition and
8. Reassemble in reverse order
10. Disposal
• Housing made of ductile cast iron
• Spring bonnet made of ductile cast iron
• Cartridge insert made of:
• Spring steel adjustment spring
• Diaphragm and seals made of EPDM
• Groove ring and sealing disc made of high-quality PU
• Stainless steel screws and nuts
Cause
Diaphragm is faulty
Spring bonnet not screwed flush
O-ring forgotten in the diaphragm piston
during assembly
Shutoff valves up- or downstream of the
pressure reducing valve are not fully open
Pressure reducing valve is not set to the
desired outlet pressure
Pressure reducing valve is not fitted in flow
direction
7
Frequency: every 1-3 years (depending on local
operating conditions)
To be carried out by an installation company
Caution !
There is a spring in the spring bonnet. It may cause
injuries if the spring is derailing.
• Make sure tension in compression spring is slak-
kened!
• Turn control adjustment screw to the left (-) until it does
not move any more
replace insert or sealing parts if necessary.
(EN-GJS-400-15 EN1563), coated with PA (polyamide)
(EN-GJS-400-15 EN1563), coated with PA (polyamide)
- DN65-100:
completely from low-lead brass (<2.2% acc. to
DIN 50930 part 6) with stainless steel valve spindle
- D15SI, D15S (DN150 - DN200):
Stainless steel
Observe the local requirements regarding correct waste
recycling/disposal!
Remedy
Replace diaphragm
Retighten the screws
Insert O-ring
Open the shutoff valves fully
Set outlet pressure
Fit pressure reducing valve in flow direction
(note direction of arrow on housing)
MU1H-1049GE23 R1215
Tabla de contenido
loading

Este manual también es adecuado para:

D15snD15si

Tabla de contenido