Single-phase control unit for rolling shutters.
It includes part of radio compatible with dynamic code transmitters and Vario Code.
Protected operations input. Output 24V DC for accessories. Protection of main feed and motor with fuse 6A.
Includes output for flashing light 220V. Auxiliary output for a second transmitter push button or garage light.
3 independent safety inputs.
Sec.1 Close / Edge may configure as photocell or safety sensitive edge (R = 8.2 Kohmios). Prepared with pho-
tocell test output with mute input or transceiver photocells.
Installation
Before proceeding with the installation make sure that mains are disconnected.
Setting the limit switch inputs
CAUTION: Before making any connections we set the table
This table has the ability to change state terminals 13 and 14. The security entrance opening (Sec.2 Open) can
be transformed into limit switch closed, the input i stop (Stop), a limit switch open door. The painting comes
with default security terminals activated If we change this option, we must continue with the next instruction
rescheduling:
1. Disconnect the power supply box (230V)
2. Place the 8 switches select options as shown (page 2, Scheme 1) in the switch box A, ie 1, 3, 5
and 7 ON and 2, 4, 6 and 8 to OFF.
3. Locate the configuration switches 4 safety inputs to OFF as shown in the table of connections
(page 2, Scheme 1) in the switch box B
4. Hold the button alternative.
5. Reconnect the box to the power supply (230V)
If the process was successful sound indicator will point to:
· An audible warning if the reconfiguration is with limit switches
· With two audible beeps if the reconfiguration is for sure.
Each time you repeat this process configuration is changed alternately, from one mode to another and vice
versa.
Description
of terminals
Power
1. Power supply 220Vac
2. Power supply 220Vac
3. Motor close
Operation
10. (+) Output + 24V AC 125 mA
11. Output 0V
12. (Sec.2 Open-Stop) Common for security during
opening and closing operation
13. (Sec.2 Open) NC opening safety contact (see
"Configuration of the safety inputs")
14. (Stop) NC stop contact (see "Configurations of
safety inputs")
15. (Test) output for photocells test
16. (Sec.1 Close / Edge) Safety Contact / Safety sensi-
tive edge during closing. Dead Man function closing
push button (see "Configurations of safety inputs")
junior D Pro
4. Motor open
5. Motor common
6. Flashing 220V
automatismos pujol
https://appceso.com
7. Flashing 220V
8. Channel 2 contact N.O.
9. Channel 2 contact N.O.
17. (Sec.Close) Contact NC closing security (see "Con-
figurations of safety inputs")
18. (Sec.1 Close / Close Edge -. Sec - P. Alt) Common
for the safety contact closing and security edges.
19. (P. Alt.) Alternate push button N.O.
Note: NO normally open / NC normally closed
13