DIEL ME 100 V2 Manual De Instalacion Y Uso página 15

Ocultar thumbs Ver también para ME 100 V2:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ENGLISH
F=2: group of eight active channels, only one level for alarm and pre alarm valid for all
channels, active fan cooling system with only one level valid for lighting H and
switching off L, control of fan cooling system also with time parameter t.
With F=2, in addition to the parameters set with F=1, is possible to set a parameter t in
minutes, t is the minimum time that must elapse before the device turn off the fan
cooling system. This guarantees a minimum time of activation for fan cooling system
independently from the value of L.
F=3: Independent programming for each channel of all levels P, A, L, H; in this mode it
is also possible to accede to RS485 section. With F=3 the device asks in sequence the
following parameters: Time t in minute, t is the minimum time that must elaps before
the device turn off the fan cooling system. This guarantees a minimum time of
activation for fan cooling system independently from the value of L. For each channel
appears the word CH(n) with n (1-8), by means of the buttons UP and DOWN you
choose if a channel is active or not, in affirmative case, it is asked to put the P and A
parameters.
Afterwards the word FnA appears, with the buttons UP and DOWN you choose if fan
cooling system is active or not for that channel, in affirmative case, it is asked to put
the L and H parameters, in case the channel is not active or fan cooling system is
deactivated for that channel the device asks the choice for the next channel, using the
same procedure for FnA, on set the second fan, in case of exclusion will be proposed
the set-up of next channel, after that, confirm all proposed parameter (not relevant in
this configuration) to finish the program procedure.
Default configurations: F=0, P=140, A=160, L=90, H=100, t=0.
Anyway the necessary time for programming is checked.
Over 1 minute from beginning of the programming phase, the same is interrupted and
not saved. (the previous set limits remain active). At the end of programming the new
data will be saved in memory,the device executes a display test and the system is
prearranged in automatic way and visualises the maximum measured temperature and
the relative channel.
DATA VISUALIZATION
Referring to F it is possible to show all parameters of interest by buttons UP and
DOWN. To show one specific parameter, or one specific measure of temperature,
-
-
15