Anomaly Warning; Remote Signalling Alarm - DV Systems ASD10 Manuel De Uso Y Mantenimiento

Secadores a expansion directa
Ocultar thumbs Ver también para ASD10:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

PARAMETER
C8
C9
NOTE: Changes entered for timing values will be effective only after exiting the programming, while changes
to other variables will be immediately effective.
Please remember that eventual changes to the configuration parameters of the machine could negatively
affect its efficiency. Thus, changes have to be arranged in collaboration with the manufacturer.
WARNING FOR USER:IT'S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION
PARAMETERS
COLLABORATION

3.1.3 ANOMALY WARNING

The controller is capable to recognize certain types of anomalies to the drying circuit. In such cases, an alarm
message will blink on the display, alternated to the current dew – point value.
MESSAGE
(BLINKING)
High Dew – point value
HtA
Very high Dew – point value
Ht2
Low Dew – point value
LtA
Interruption or short circuit on
PF1
the PTC probe input line
ESA
Energy saving mode activated
ES2
Series of alarms very close to
ASt
Note: PF1 has priority on all other alarm messages.
3.1.4
REMOTE SIGNALING ALARM
Cod. 710.0138.20.00 Rev 05B – 03.2016
DESCRIPTION
Delay between condensate
discharges
Time required for condensate
discharge
OF
THE
ELECTRONIC
CAUSE
(delayed alarm)
(immediate alarm)
each other
The dryer control board is equipped with a digital output for the remote signalling alarm.
This digital output is controlled by a relays configured as normally open: when an alarm is
detected, this relays closes a circuit.
Proceed as follows to activate a remote alarm output:
1. The User must provide a signaller in compliance with output relays electrical
features (solenoid coil, light bulb, acoustic signaller, ...).
2. Disconnect the dryer from electrical power supply, remove cover and left side panel.
3. Connect the signaller to the terminal blocks (See PIC.3).
1 ÷ 999 (min)
1 ÷ 999 (sec)
CONTROLLER
OUTPUTS
Alarm output ON
Refrig. Compressor output OFF
Fan output ON
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output OFF
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output ON
Discharge cycle standard
RANGE
SET VALUE
WITHOUT
AUTHORIZATION
ACTIONS
Resettable by switching off the
control board when dew-point
returns to preset range.
If it persists call our Service
Centre.
Automatic reset when dew-
point returns to preset range.
If it persists call our Service
Centre.
Resettable by switching off the
control board and replacing the
faulty probe.
Call our Service Centre.
No action necessary.
Automatic Reset
Call our Service Centre.
ENGLISH
1
1 - 3
AND
7