Specifications - Tripp-Lite S3MT Serie Manual Del Propietário

Transformadores de entrada trifásica
Ocultar thumbs Ver también para S3MT Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5. Specifications

Models
Description
Transformer Type
Input
Input Voltage
Input Voltage Operational Range and De-Rating
Input Amps
Input Connections
Input Configuration
Input Connection Type
Rated AC Input Frequency
Frequency Range and Derating
Voltage Selection
Voltage Drop: Ratio Ouput, No Load to Full Load
Inrush Current
Input Isolation
Output
VA Rating
Transformer Output Voltage
Output Amps
Transformer Output Breaker Rating
Output Watts Detailed
Output Connections
Output Connection Type
Output Configuration
Input Tranformer, Output Isolation
Operation
Over-Temperature Warning LED Light (Red)
Over-Temperature Protection Reset Device
Insulation Class
Temperature Rise
Full Load Efficiency
Half Load Efficiency
Physical Info
Unit Height
Unit Width
Unit Depth
Unit Weight
S3MT-20K480V
3-Phase 20k Input Isolation
Transformer, Delta 480V/208V Wye
-45%, +25% at 40 % load
-20%, +25% at 100 % load
35A
3-Wire (L1, L2, L3 + PE)
≤300A (10 ms)
20kVA
208/120V, (3-Phase, 4-Wire)
75A
80A
20,000W
4-Wire (L1, L2, L3, +N, +PE)
Turns ON at 160°C ±5°C,
i.e. a range of 155°C to 165°C (311°F to 329°F)
Turns OFF at 125°C ±5°C,
i.e. a range of 248°F to 266°F (120°C to 130°C)
Transformer output turns OFF at temperatures of 160°C ±5°C, i.e.
a range of 155°C to 165°C (311°F to 329°F).
The transformer output breaker can be turned ON manually when
the warning light turns OFF.
95.00%
96.50%
430 lb. (195 kg)
14
S3MT-30K480V
3-Phase 30k Input Isolation
Transformer, Delta 480V/208V Wye
Dry-Type
480V
Delta
Terminal Block
50/60 Hz
40~70 Hz
No
≤ 3%
≤1010A (10 ms)
Yes
30,000W
Terminal Block
Wye
Yes
180°C
125°C
95.20%
97.50%
47.2 in. (1200 mm)
17.4 in. (442 mm)
33.5 in. (850 mm)
617 lb. (280 kg)
51A
30kVA
83A
125A
Tabla de contenido
loading

Este manual también es adecuado para:

S3mt-20k480vS3mt-30k480v