3. Installation
3.6 Power Cables
The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical
codes.
WARNING!
UPON STARTUP, ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL
ISOLATORS CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTRIBUTION PANEL.
ENSURE THESE SUPPLIES ARE ELECTRICALLY ISOLATED AND POST ANY NECESSARY WARNING SIGNS TO
PREVENT INADVERTENT OPERATION.
Cable Sizes
UPS Model
Gauge
10 AWG
S3MT-20K480V
Max.
4 AWG
6 AWG
Max.
S3MT-30K480V
3 AWG
Cable Sizes (THHW wiring at 75°C)
AC Input
AC Output
Torque
Gauge
4 AWG
6.5 N•m
Max.
4 AWG
3 AWG
6.5 N•m
Max.
3 AWG
Neutral
Torque
Gauge
4 AWG
6.5 N•m
Max.
4 AWG
3 AWG
6.5 N•m
Max.
3 AWG
10
Grounding
Torque
Gauge
4 AWG
6.5 N•m
Max.
4 AWG
3 AWG
6.5 N•m
Max.
3 AWG
Torque
6.5 N•m
6.5 N•m