Specifications; Product Registration And Regulatory Compliance - Tripp-Lite SmartPro SMART5000RT3U Manual Del Propietário

Ocultar thumbs Ver también para SmartPro SMART5000RT3U:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Specifications

Model
Nominal voltage and input range:
Nominal input frequency and tolerance:
Nominal output voltage:
Nominal output frequency:
Output voltage regulation in line mode:
Output voltage regulation in battery mode:
Nominal output power in W / VA:
Output voltage waveform:
Maximum output current @ P . F.
Maximum harmonic distortion of output voltage at full resistive load:
Efficiency with nominal load:
Maximum operating altitude at 100% of nominal power:
Online overload capability:
Overload capacity in battery mode:
Current limitation:
Autonomy time at full load:
Battery recharge time:
Transfer time:
Outlets:
Maximum input current:

Product Registration and Regulatory Compliance

Product Registration
Visit tripplite.com/warranty today to register your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
FCC Notice, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a resi-
dential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must use shielded cables and
connectors with this equipment. Any changes or modifications to this equipment not expressly approved by Tripp Lite could void the user's authority to operate this equipment.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the
product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The
series number should not be confused with the marketing name or model number of the product.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products.
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V
: DC Voltage
SMART5000RT3U
208V~; 151-260V~
60 Hz (+/- 5 Hz)
208V~ sinusoidal in line mode and 208V~ sinusoidal in battery mode
60 Hz (+/- 0.5 Hz)
208V~/120V~ (+20% / - 10%)
120V~ (+/-5%)
4000W / 5000VA
Sinusoidal in line mode and in battery mode
22A @ 208V~ / 38A @ 120V
(24A @ 208V~ / 40A @ 120V WITH 50A PLUG OR HARDWIRED INPUT)
P .F. = 0.8
6561 ft. (2000 m)
125% for 10 minutes
105% @ 0.5 seconds
Input 1x 30A; Output: 3x 15A
16 minutes @ 4000W
2 milliseconds typical (4 milliseconds max)
10 X 5-15R, 2 X 5-20R, 1 X L6-30, 1 X L14-30 outlets
with battery backup, regulation and surge
24A (27A with 50A Plug or Hardwired Input)
9
3%
94%
4 hours
Tabla de contenido
loading

Tabla de contenido