16: Inverter B voltage adjustment
Interface
17: Inverter C voltage adjustment
Interface
18: Output A voltage calibration
Interface
19: Output B voltage calibration
Interface
20: Output C voltage calibration
Interface
USER MANUAL – OPTIMA-33-T10 10K-80K
Setting
Parameter 2: you may choose Add or Sub to adjust inverter B voltage*.
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
*It will display number 1 under
Setting
Parameter 2: you may choose Add or Sub to adjust inverter C voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default value is 0V.
*It will display number 2 under
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output A voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3: it shows the internal measurement value of the output B voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
*It will display number 1 under
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output C voltage, and you
can calibrate it by pressing Up or Down according to the measurement from an external
voltage meter. The calibration result will be effective by pressing Enter. The calibration
range is limited within +/-9V. This function is normally used for parallel operation.
*It will display number 2 under
or
to represent inverter B voltage.
or
to represent inverter C voltage.
to represent the output B voltage.
to represent the output C voltage.