( 1 ) Insert the drain hose into the drain hole and tighten it with tapes, as shown in Fig 4.3.2.
( 2 ) Tighten the pipe clamp, with the distance between screw nut and hose smaller than 4mm.
①metal clamp(accessory)
②drain hose(accessory)
( 3 ) Use sealing plate to make the pipe clamp and hose insulated, as shown in Fig.4.3.3.
①metal clamp(accessory)
②thermal sponge(accessory)
( 4 ) When connecting several drain pipes, follow the instruction as indicated in Fig 4.3.4. Choose the
drain collecting pipe that matches with unit capacity.
5
(5)For indoor units that have high pressure at the outlet of drain pipe, use water-sealed joint.
6
For indoor units that have high pressure at the outlet of drain pipe, use water-sealed joint.
7
Install the water-sealed joint according to Fig.4.3.5.
8
Each unit should be installed with one water-sealed joint.
9
The horizontal pipe can be connected to vertical pipe in the same level; please select the
connection way as shown in following fig.