APPENDIX
Minimum floor area: Amin (m
When an outdoor unit using R32 refrigerant is combined with this indoor unit, do not install the indoor unit in a poorly
ventilated space that is smaller than the minimum floor area (Amin).
For refrigerant quantity, refer to Fluorinated Greenhouse Gases label on the outdoor unit.
For the minimum floor area (Amin) of this indoor unit, refer to table below.
Total refrigerant quantity
Floor standing unit
M (kg)
Amin (m
0.90
1.00
1.10
1.20
1.30
No requirements
1.40
1.50
1.60
1.70
1.80
1.84
4.64
1.90
4.79
2.00
5.04
2.10
5.29
2.20
5.54
2.30
5.80
2.40
6.05
2.50
6.30
2.60
6.55
2.70
6.80
2.80
7.05
2.90
7.31
3.00
7.56
3.10
7.81
3.20
8.06
3.30
8.31
3.40
8.57
3.50
8.82
3.60
9.07
3.70
9.32
3.80
9.57
3.90
9.82
4.00
10.08
4.10
10.33
4.20
10.58
4.30
10.83
4.40
11.08
4.50
11.33
4.60
11.59
4.70
11.84
4.80
12.09
4.90
12.34
5.00
12.59
147-EN
2
)
Total refrigerant quantity
Floor standing unit
2
M (kg)
)
Amin (m
5.10
12.85
5.20
13.10
5.30
13.35
5.40
13.60
5.50
13.85
5.60
14.10
5.70
14.36
5.80
14.61
5.90
14.86
6.00
15.11
6.10
15.36
6.20
15.62
6.30
15.87
6.40
16.12
6.50
16.37
6.60
16.62
6.70
16.87
6.80
17.13
6.90
17.38
7.00
17.63
7.10
17.88
7.20
18.13
7.30
18.38
7.40
18.64
7.50
18.89
7.60
19.14
7.70
19.39
7.80
19.64
7.90
19.90
8.00
20.15
8.10
20.40
8.20
20.65
8.30
20.90
8.40
21.15
8.50
21.41
8.60
21.66
8.70
21.91
8.80
22.16
8.90
22.41
9.00
22.66
-
-
-
-
-
-
25
2
)
20
15
10
5
0
0.0
– 74 –
1.0
2.0
3.0
4.0
5.0
6.0
M [kg]
7.0
8.0
9.0
10.0