Safety Instructions - Danfoss ECflex 100T Guia De Instalacion

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
Installation Guide
1
Introduction
In this installation manual, the phrase "heating cable" refers
to heating cables in readymade lengths; heating cables
on drums; heating cables on mesh; and preshaped taped
heating cables.
2

Safety instructions

Heating cables must always be installed according to
local building regulations and wiring rules as well as the
guidelines in this installation manual.
• De-energize all power circuits before installation and
service.
• Residual current device (RCD) protection is required. RCD
trip rating is max. 30 mA.
• The screen from each heating cable must be earthed in
accordance with local electricity regulations
• Heating cables must be connected via a switch providing
all pole disconnection.
• The heating cable must be equipped with a correctly sized
fuse or circuit breaker according to local regulations.
• Never exceed the maximum heat density (W/m or W/m²)
for the actual application.
3
Installation guidelines
• It is not recommended to install heating cables at
temperatures below -5°C.
• Heating cable bending diameter must be at least 6 times
the cable diameter. Do not bend connections.
4
Mechanical class
M1— For use in applications with low risk of mechanical
damage according to IEC 60800:2009, e.g. installed on even
surfaces and embedded in screeds with no sharp objects.
M2 — Can be used in applications with high risk of mecha-
nical damage according to IEC 60800:2009.
4
Heating cables
To get the full installation guide, warranty registration,
product information, tips & tricks, addresses, etc.
visit www.danfoss.com
and www.gb.fhemanuals.danfoss.com.
• Strongly recommended to use the heating cable together
with an appropriate thermostat to secure against
overheating.
• Caution! Do not use M1 classified cables in areas subject
to high mechanical loads or impact, such like outdoor
applications, on steel reinforcing grids, in concrete with
sharp stones, roof and gutters, etc.
The presence of a heating cable must
• be made evident by affixing caution signs in the fuse box
and in the distribution board or markings at the power
connection fittings and/or frequently along the circuit line
where clearly visible (tracing).
• be stated in any electrical documentation following the
installation.
• Free end from cold lead must be protected by installer to
avoid water from coming in.
C — High mechanical strength according to IEC 60800:1992.
MMM — Marking for high mechanical protection class
according to NF C 32-330:2002