Note: The detector must be in local or diagnostic mode to perform the link quality test.
In diagnostic mode, if you press the Test button for more than 10 seconds, an alarm
message is sent to the panel and a Temporal-3 alarm signal is sounded. After this
sequence is completed, the device enters Alarm in Memory mode. To preserve
battery life, the device clears the indication after 30 minutes if it has not been cleared
on the panel.
B. If you press the test button for 4 seconds and then release, at the end of the
diagnostic test the LED blinks three times. The following table indicates the received
signal strength.
LED
Green LED
Orange LED
flashes
flashes
Response
Strong
Good
Reception
IMPORTANT! Reliable reception must be confirmed. Therefore, poor signal strength is
not acceptable. If you receive a poor signal from the device, re-locate it, and re-test until
a good or strong signal strength is received. See the alarm system installation manual
for detailed diagnostic tests. For UL/CUL installations, the test results must be strong.
Owner's Maintenance
This detector is designed to require minimal maintenance. If the plastic housing is greasy,
wipe gently with a soft cloth slightly dampened with soapy water.
Never disassemble the detector; there are no user-serviceable parts inside the unit.
You may only remove the backplate to replace the battery if not serviced by an
installer. When replacing the battery, follow the instructions specified in the Installation
Instructions.
Never paint the detector. Paint may interfere with the proper operation of the
detector. If you are planning renovations or repainting, take precautions to avoid
dust, paint, or chemical contamination of the detector.
Installation, testing and maintenance procedures shall be in accordance with
NFPA72, CAN/ULC-S524, and CAN/ULC-S536
CAN/ULC
Specifications
Regulatory Listings: FCC/ISED Canada/CE; UL521/ULC-S530
Diameter: 5 in (127 mm)
Height: 2 in (50.8 mm)
Red LED
No flashes
flashes
Paired, no
Poor
communication
Weight (including battery): 7 oz (198.4 g)
Color: White
Audible Signal (ANSI Temporal 3): 85 dBA at 10 feet (3.05 m) minimum
in alarm
Heat Alarm Threshold: 135 ºF (57.5 ºC)
Humidity: 5 % - 93 % RH, non-condensing
Voltage: 3V DC
Approved Batteries: One battery: Panasonic CR123A or Duracell
DL123A
Supervisory Transmission Frequency: 128 s intervals
LIMITED WARRANTY
Digital Security Controls warrants that for a period of 12 months from the date of purchase, the
product shall be free of defects in materials and workmanship under normal use and that in
fulfilment of any breach of such warranty, Digital Security Controls shall, at its option, repair or
replace the defective equipment upon return of the equipment to its repair depot. This
warranty applies only to defects in parts and workmanship and not to damage incurred in
shipping or handling, or damage due to causes beyond the control of Digital Security Controls
such as lightning, excessive voltage, mechanical shock, water damage, or damage arising out
of abuse, alteration or improper application of the equipment.
The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of any
and all other warranties, whether expressed or implied and of all other obligations or liabilities
on the part of Digital Security Controls. Digital Security Controls neither assumes responsibility
for, nor authorizes any other person purporting to act on its behalf to modify or to change this
warranty, nor to assume for it any other warranty or liability concerning this product.
In no event shall Digital Security Controls be liable for any direct, indirect or consequential
damages, loss of anticipated profits, loss of time or any other losses incurred by the buyer in
connection with the purchase, installation or operation or failure of this product.
Warning: Digital Security Controls recommends that the entire system be completely tested
on a regular basis. However, despite frequent testing, and due to, but not limited to, criminal
tampering or electrical disruption, it is possible for this product to fail to perform as expected.