Do not create model numbers from this chart as all features are not available on all models
ll
TE = Transient Eliminator, Listed Type 2 SPD in
NEMA 1/3R/04/12 enclosure
XTE = Transient Eliminator, Recognized Type 4
SPD on backplane for installation within
gear in Type 2 installation
(display on 6' cable)
Voltage Code for Electrical System
Common North American Systems:
1 = 240/120V Split Phase - 1Ø 3W+Grnd (Fig 1)
2 = 208Y/120V Wye - 3Ø 4W+Grnd (Fig 2)
3 = 240/120V High Leg Delta (B High) (Fig 3)
4 = 480Y/277V Wye - 3Ø 4W+Grnd (Fig 2)
5 = 480V Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye
8 = 600Y/347V Wye - 3Ø 4W+Grnd (Fig 2)
Other Available Systems -
Confirmation encouraged:
11 = 120V Single Phase - 1Ø 2W + Grnd (Fig 5)
12 = 240V Single Phase - 1Ø 2W + Grnd (Fig 5)
51 = 480V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
6 = 240V Delta - 3Ø 3W+Grnd (Fig 4)
61 = 240V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
7 = 380Y/220V Wye - 3Ø 4W+Grnd (Fig 2)
9 = 600V Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye
91 = 600V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
Figure 1
Figure 2
Phase A (BLK)
Hot (BLK)
}
V
A
}
Neutral (WHT)
V
Hot (BLK)
Ground (GRN)
SPLIT
WYE
2 Hots, 1 Neu, 1 Grnd
3 Hots, 1 Neu, 1 Grnd
TYPICAL PARALLEL
Figure 2
CONNECTED SPD ON
ELECTRICAL PANEL
To Protected
Loads
A
B
BREAKER
N
All manuals and user guides at all-guides.com
TABLE 1: MODEL NUMBER DECODER
l
/
...
/
Figure 3
Phase A (BLK)
Phase B (BLK)
Phase B (ORNG)
B
V
Neutral (WHT)
N
}
Phase C (BLK)
V
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
C
Ground (GRN)
HI-LEG DELTA (B High)
3 Hots, (B HIGH),
1 Neu, 1 Grnd
C
Advanced Protection Technologies
Phase A
G
Phase B
Surge Counter
Phase C
Service
Test
Count
Reset
Silence
ll
HP
/
Model Family
HP = HP Family
120kA rating standard
80kA rating standard
Enclosure Rating
04 = Standard: NEMA 1/3R/04/12 (size: 12" x 12" x 7.5")
FM = Flush Mount Enclosure, NEMA 1 only
(wall cavity size: 12" x 12" x 6")
4X = NEMA 4X Non-Metallic (size: 14" x 12"x 6")
(polycarbonate, display inside clear front door)
4S = NEMA 4X Stainless Steel (size: 12" x 12"x 6")
(display inside door)
Figure 4
Phase A (BLK)
V
Phase B (BLK)
Phase C (BLK)
Ground (GRN)
DELTA & HRG WYE
3 Hots, 1 Grnd
Storage Environment
This SPD should be stored in a clean, dry environment.
Storage temperature range is -40°C (-40°F) to +60°C
(+140°F). Avoid exposure to high condensation.
Unpacking & Preliminary Inspection
Inspect the entire shipping container for damage or signs
of mishandling. Remove the packing materials and further
inspect the unit for any obvious shipping damages.
If any damage was found and is a result of shipping
or handling, immediately file a claim with the shipping
company and forward a copy to APT.
Storage Environment
This SPD should be stored in a clean, dry environment.
Storage temperature range is -40°C (-40°F) to +60°C
(+140°F). Avoid exposure to high condensation.
l
/
...
Option Suffixes (Seperated by slashes / )
CX = 120kA Option
CL = 160kA Option
DC = Dry Contacts
Two sets Form C on terminal strip
SC = Surge Counter
Available Accessory (order separately)
RM = Remote Monitor
Figure 5
Figure 6
}
Hot (BLK)
V
Neutral (WHT)
Ground (GRN)
SINGLE POLE
CORNER GROUND
1 Hot, 1 Neu, 1 Grnd
DELTA (B grounded)
2 Hots, 1 Grnd
V
Phase A (BLK)
Phase C (BLK)
Ground (GRN)
3