Grounding
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC
FLASH
Failure to properly ground the passive harmonic filter
as per all applicable codes and standards will result in
serious personal injury or death.
To ensure safe operation, the HPS Centurion P
Passive Harmonic Filter must be properly grounded
before energizing. Each filter will come equipped with a
designated main grounding location.
Protection
The HPS Centurion P Passive Harmonic Filter should
be protected by a user supplied circuit breaker or fused
disconnect on the input per electrical code requirements.
Field Wiring
All of the connection points of the HPS Centurion P
Passive Harmonic Filter are clearly marked as follows:
•
A1, B1 and C1 should be connected to phases A, B
and C of power supply (branch circuit breaker).
•
A2, B2 and C2 should be connected to phases A, B
and C of the load.
Refer to Appendix A for suggested cable entry
locations.
Commissioning/Testing
Field inspection start up and testing shall be
performed by a qualified technician from the owner,
contractor or HPS.
In order to quantify the power quality improvement
due to the HPS Centurion P Passive Harmonic Filter,
measurements can be taken before and after. Before
connecting the Passive Harmonic Filter into the system
you can use a power quality analyzer (e.g. Fluke 1736 or
Hioki 3196) to obtain a baseline for total harmonic voltage
distortion, total harmonic current distortion, power factor,
etc.
Installation, Operation, and Maintenance Guide - Low Voltage Passive Filters
HPS Centurion P
Disconnect
Passive Harmonic
Filter
SUPPLY
Power
Quality
Analyzer
After connecting the HPS Centurion P Passive Harmonic
Filter, the power quality analyzer can be connected to
input disconnect. Care should be taken that the before
and after measurements are taken at the same speed and
load condition to make a valid comparison. The following
table can be used to record the before and after readings:
A2 B2 C2
Reactor 2
A1 B1 C1
Reactor 1
A3
B3
C3
HPS Centurion P Passive Harmonic Filter Connection
Diagram
Before
Voltage
Current
kW
kVA
Power Factor
THDv
THDi
VFD
MOTOR
Non-linear Load
Source
600V/60Hz
Capacitors
can be
C
C
connected in
C
Star or Delta
After
6