Siku KSA YE Serie Instrucciones De Uso página 5

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 32
EN
CONNECTION TO POWER MAINS
For connection of the fan with a power cable and no adapter, follow the wiring diagram in fig. 6.
The models KSA 100/125/150/160/200 are equipped with integrated motor overheating protection and
require no extra protection measures.
ATTTENTION! The KSA 250, KSA 315 models with a power cable and no adapter have no
overheating protection!
The recommended wiring diagram for the KSA 250 and KSA 315 fan with motor overheating protection
are shown in fig. 7.
The terminals TW1, TW2 are the electrical leads of the normally closed contact of the motor overheating
protection. Connect the contact in series to power circuit of the magnetic starter coil KM1 that starts the
motor after pressing the button S1. After the motor overheating the contact gets broken and switches the
starter coil off to cut power off and stop the motor.
The automatic circuit breaker QF, the magnetic starter KM1, the control knobs S1 and S2 are not included
into the delivery set and must be installed by the users.
Designation keys:
L, N connection terminals;
PE ground terminal;
QF automatic circuit breaker;
S1 ON button;
S2 OFF button;
X1 input terminal block;
KM1 magnetic starter;
TW1, TW2
overheating protection leads.
MAINTENANCE
Clean the fan surfaces regularly of dust and dirt, at least once in 6 months, fig. 10 12.
Disconnect the fan from power mains prior to any maintenance operations.
Clean the fan with a soft cloth or a brush wetted in mild detergent solution.
Avoid liquid dripping on the electric components, fig. 13.
While cleaning the fan be careful not to displace the impeller counter weights.
Wipe the surfaces dry after cleaning.
STORAGE AND TRANSPORTATION RULES
Transportation is allowed with any vehicle provided that the fan is protected against mechanical or weather
damage. Store the delivered device in the manufacturer's original packing box in a dry ventilated premise
0
0
with the temperature range from +5 C up to + 40 C and relative humidity less than 80%. The storage
environment must not contain dust, acid or alkali vapours that may cause corrosion of the fan components.
5
Tabla de contenido
loading

Este manual también es adecuado para:

Ksa ye r serieKsa ye un serieKsa ye u1n serieKsa ye p serie

Tabla de contenido