2.1 TYPE OF PROTECTIONS
Ex db eb IIC T6,T5,T4 Gb or Ex d e IIC T6,T5,T4 Gb
Ex db eb mb IIC T6,T5,T4 Gb or Ex d e mb IIC T6,T5,T4 Gb
Ex eb mb IIC T6,T5,T4 Gb or Ex e mb IIC T6,T5,T4 Gb
Ex tb IIIC T80°C, T95°C, T130°C Db
The marking is related to the type of protection of the components installed into the control station.
Temperature class and maximum surface temperature is marked on the label.
The cable shall be suitable to the maximum temperature (Tcable) indicated on the marking label.
2.2 EXAMPLE MARKING LABEL
Figure 2

2.3 WARNING LABEL

Do not open when energized or in presence of explosive atmospheres
WARNING: Use cables suitable for temperature of xxx°C, ( See the marking label ).
2.4 CERTIFICATES
Atex Certificate -IMQ 19 ATEX 034 X
IECEx Certificate - IECEx IMQ 19.0005 X
2.5 ENCLOSURES DEGREE OF PROTECTION
IP66
The equipment can be marked with the lowest degree of protection dependant by certified components mounted on the equipment.
(See the marking label on the product).
2.6 AMBIENT TEMPERATURE RANGE
The equipment is certified for a maximum ambient temperature range -60°C / +95°C with appropriate terminals and accessories.
The ambient temperature range will be limited by the component (terminal, actuator, switch, breath/drain valve
etc.) with the worst characteristics.
The ambient temperature is marked on the label and the control station should not be used outside this range.

3. INSTALLATION

Installation shall be carried out by suitably trained personnel in accordance with the applicable code of
practice (e.g. IEC / EN 60079-14) and the provisions of the national safety and accident prevention regulations
and this instruction manual.