4. Control mode setting
n Use the CONTROL_MODE_SW to set the control mode you
want from 0~F.
CONTROL_MODE_SW
Ú Indoor control priority
Central control > Dry contact For Economizer > Wired/Wireless remote controller, indoor unit button
Ú Dry contact For Economizer controls the indoor unit according to the applicable mode when there is
a change in input of A and B.
n Description of each control mode
1) Disable using Dry contact For Economizer
CONTROL
Input A
MODE SWITCH
0
Ú Set this when the Dry contact For Economizer is connected but not used.
Input B
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Operating mode
The indoor unit cannot be controlled through the
Dry contact For Economizer
No change in indoor unit condition
Setting and using method
Installation Manual 13