ELECTRICAL CONNECTIONS OF THE INSTRUMENT
Follow the rules below for construction of the electrical installation relative to the charge separator:
• Use insulated wire terminals for connection to the charge separator terminals.
• Use wires with an adequate cross-section and as short as possible.
• The electrical connections must be made in compliance with local rulings on electrical installations.
WARNING: before connecting the batteries, check the polarity of the cables carefully.
WARNING: before connecting or disconnecting wires from the electrical terminals of the charge separa-
tors make sure that the wires are not live.
WARNING: the use of wires with an inadequate cross-section and incorrect connection of the terminals or
of the electrical joints can cause dangerous overheating of the connections and of the wires.
Minimum recommended wire sections are given below:
Current
0 ÷ 40 A
40 ÷ 80 A
80 ÷120 A
(1)
Working temperature of wire 70°C .
DCS - REV001A
Minimum cross section of wire
25 mm
2
(AWG 3 )
2
35 mm
(AWG 2)
50 mm
2
(AWG 0)