If it is necessary to modify the operating time of the motors, programming must be carried
out when the gate is closed, as follows: use the SEL key to move to the flashing T.MOT
LED. then press the SET key briefly. Motor 1 will start the opening cycle; in correspond-
ence with the point desired to start deceleration press the SET key again: the T. MOT. LED.
will start flashing more slowly and Motor 1 will decelerate; when the desired position is
reached, press the SET key to complete the opening cycle. The T. MOT LED will now start
flashing normally again and Motor 2 will begin its opening cycle: repeat the operations to
program the work time for Motor 2, After programming the opening times for the motors,
Motor 2 will start its closing cycle: repeat the same instructions as above for program-
ming the closing cycle of Motor 2 and then for Motor 1. If you do not want the control unit
to decelerate, when the opening and closing phase is finished, press the SET key twice
during programming, instead of just once.
During programming it is possible to use the radio control key located on the control unit,
instead of the SET key, only if previously memorised.
6) T. MOT. PED: (Programming a pedestrian operating time of 4 minutes max.)
The control unit is factory supplied with a predefined (Pedestrian) Motor 1 operating time
of 10 sec. without deceleration.
If it is necessary to modify the pedestrian operating time, programming must be carried out
when the gate is closed, as follows: use the SEL key to move to the flashing T.MOT PED.
LED, then press the SET key briefly. Motor 1 will start the opening cycle; in correspondence
with the point desired to start deceleration, press the SET key again: the T. MOT. PED. LED
will start flashing more slowly and Motor 1 will decelerate; when the desired position is
reached, press the SET key to complete the opening cycle. At this point the T. MOT PED. LED
will start flashing at its standard pace again and the Motor 1 will begin the closing phase;
repeat the above operations for the closing phase. If you do not want the control unit to
decelerate, when the opening and closing phase is finished, press the SET key twice during
programming, instead of just once.
During programming it is possible to use the radio control key located on the control unit,
instead of the SET key, only if previously memorised.
7) T. PAUSA: (Automatic closing time programming max. 4 minutes)
The control unit is factory supplied without automatic closing. If you wish to enable auto-
matic closing, proceed as follows: using the SEL key to move to the flashing T. PAUSA LED,
press the SET key briefly, then wait for the amount of time you wish to set for automatic
closing; briefly press the SET key again, and in that moment the automatic closing time
will be stored and the T. PAUSA LED will stay on steady. If you wish to restore the initial
condition ( without automatic closing ), move to the flashing T. PAUSA LED, then press the
SET key twice within 2 seconds; the LED will shut off and the operation will be complete.
During programming the radio control key of the control unit can be used instead of the
SET key, if stored previously.
8) T. RIT. ANTE: (Programming door delay of 15 sec. Max.)
The control unit is supplied by the manufacturer without gate delay during opening and
closing. If it is necessary to enter a gate delay time, programming must be carried out
when the gate is closed, as follows: use the SEL key to move to the flashing RIT. ANTE
LED, press the SET key, wait for desired interval of time, then press the SET key again: the
gate delay time opening will be stored, at 2 seconds, of the delay time of the door closing
for the time programmed and the RIT. ANTE LED is steady.
To restore the initial configuration (without door delay), go to the RIT. ANTE LED when
flashing then press the SET key twice within 2 seconds, the LED goes off and the opera-
tion is completed.
EXTENDED MENU 1
The control unit is supplied by the manufacturer with the possibility of selecting only the
main menu functions.
To enable the functions listed in extended menu 1, proceed as follows: press the SET
button and hold for 5 seconds, after which the T. PAUSA LED and RIT. ANTE LED will flash
alternately. You have 30 seconds to select the functions of Extended Menu 1 using the
SEL and SET buttons. After another 30 seconds, the control unit returns to the main menu.
EXTENDED MENU 1
Reference LED
LED Off
A) AUT / P-P
PGM remote = OFF
B) CODE
Test Photocell = ON
C) CODE PED.
Mant. Pressure = OFF
D) INB.CMD.AP
Water Hammer = OFF
E) T. MOT.
Closing Hammer = OFF
F) T.MOT.PED.
Safety Device 2
G) T. PAUSA
Alternate ON/OFF flashing light
H) RIT. ANTE
Flashing beacon ON/OFF in alternation
A) AUT / P-P (Remote programming of radio control):
The control unit allows the transmission code to be programmed, without using the SEL
button directly on the control unit, but remotely.
The remote transmission code can be programmed as follows: continuously sending a
previously-memorised radio control code for more than 10 seconds. At this point the
control unit switches to programming mode, as described above for the CODE LED in
the main menu.
The control unit is supplied by the manufacturer with the remote transmission code
programming function disabled. If you wish to enable the function, proceed as follows:
check that Extended Menu 1 is enabled (RIT. ANTE LED and T. PAUSA LED start flashing
alternately, with the SEL key positioned on the flashing of AUT/ P-P LED then press the
SET key, the AUT/P-P LED will simultaneously stays on steadily and programming is
completed. Repeat the procedure to restore the previous configuration.
B) CODE (Test Photocell):
The control unit is supplied by the manufacturer with photocell Test programming enabled
(in accordance with Standard EN 12453). If you wish to disable the function proceed as
follows: check that Extended Menu 1 is enabled (T. PAUSA and RIT. ANTE LEDs flashing
alternatively), with the SEL key position on the flashing of CODE LED then press the SET
key, the CODE LED will simultaneously stay on steady and programming is completed.
Accordingly, the photocell test will not be carried out, therefore even if not connected (if
unused, DS1 and DS2 inputs must be jumped), the control unit is enabled for operation.
Repeat the procedure to restore the previous configuration.
17
LED On
PGM remote = ON
Test Photocell= OFF
Mant. Pressure = ON
Water Hammer = ON
Closing Hammer = ON
Block Input