GB
confi guring the settings
PARAMETER
SEQU CHANGE
SEQ SW TIME
52
DISPLAY SCREEN
PRESS THE PROGRAMMING BUTTON "
TURN THE CONTROL AND SELECT THE "SEQU CHANGE" PARAMETER
PRESS THE PROGRAMMING BUTTON "
SEQU CHANGE
0 1
PRESS THE PROGRAMMING BUTTON "
URN THE CONTROL AND SELECT THE "SEQ SW TIME" PARAMETER
PRESS THE PROGRAMMING BUTTON "
SEQ SW TIME
2 0 0
PRESS THE PROGRAMMING BUTTON "
URN THE CONTROL AND SELECT THE "RETURN" PARAMETER
PRESS THE PROGRAMMING BUTTON "
FIGURE
DESCRIPTION
"
" (
RED LED ON)
Ruotare la manopola e impostare la selezione
Turn the control and set the sequence in
which to start up the heaters:
=> 01 : heater order 1 only (SEQUENCE 1);
=> 02 : heater 2 order only (SEQUENCE 2);
=> 03 : switching between sequences 1 and
2 according to the running time of the fi rst
heater in the selected sequence;
=> 04 : 1/3 <-> 2/3 switching for heaters with
diff erent nominal power;
=> 05 : the heaters move position when the
time comes for the order to change; that is,
the fi rst heater in the sequence is then made
the last in the next sequence
(e.g. 12345678, then 23456781, then
34567812, etc.);
=> 06 : sequence inversion depends on the
length of time each generator is run (the
generator that is run for the least amount of
time starts fi rst, etc.)
You are advised to set at 05 or 06 to distribute
the operating time evenly for all the heaters.
"
" (
RED LED ON)
Confi guration of the time for switching the
200
heater start-up sequence
"
" (
TO EXIT)