Approved installation positions
Precision class R xxxH / xxxV
H
V
H = Horizontal, V = Vertical
Installation
!
Only by qualified skilled craftsmen or specia-
list personnel trained by Techem!
Prerequisites:
•
Meter with radio module: Distance from power
supply lines ≥ 300 mm
•
Shut-off valves for later meter swap
•
Switch off devices connected on the supply net-
work in order to avoid damage from overpressure
or overtemperature.
Procedure:
1
Close the valve in front of the water meter.
2
Bleed lines.
3
Close the valve behind the water meter, empty
the lines if the valve is missing.
4
Release the screw joint using appropriate
tools.
5
!
When installing in plastic conduits, always use
the EPDM seals provided especially for this
purpose.
Article no. 199 133 for
Article no. 199 134 for 1"
7
Observe the installation position.
Use new seals which are approved for drinking
water. Do not screw the screw joint on too tight-
ly.
!
EPDM seals: When using EPDM seals, tighten
the union nut by hand and then
8
Open the tap connections.
Open the valve behind the water meter.
9
Open the valve in front of the meter slowly.
10
Implement a function check.
11
Close tap connections and check the leak
tightness of the system.
12
Seal the screw joint connectors.
www.techem.de
V
V
6
/
"
3
4
/
to 1 turns.
1
2
13
Switch on any devices connected on the supply
network again.
14
Keep the operating instructions on-site.
!
Radio upgrade of AP vario: see separate
document.
Operation and maintenance
!
Observe nominal operating conditions ac-
cording to the Declaration of Conformity and
information on the devices!
Meter reading
Black figure drum: Full m
Red digits following the decimal point: Full litres
Maintenance and cleaning
If used in accordance with its intended use, the
water meter is maintenance-free for the duration of
use.
Legal notice
Radio module radio CE conformity
Techem Services GmbH herewith declares that the
radio module radio meets the basic requirements
and relevant regulations of Directive 2014/53/EU
(RED).
Complete Declaration of Conformity:
www.techem.de/funkgeraete
Manufacturer
E. Wehrle GmbH, Obertalstraße 8,
D-78120 Furtwangen, www.wehrle.de
Disposal
Dispose of meters professionally!
If you dispose of them yourself, be certain to obser-
ve the following:
The optional radio module contains a battery and
therefore may not be disposed of as normal house-
hold waste!
3