OPERATION
• Valve opens and closes automatically when
hands are presented in the detection zone.
Comfort shut-off delay is 3 seconds.
• Anti-Legionella duty flush: automatic duty
flush for 45 seconds every 24 hours after the
last use.
• Anti-blocking safety: a safety delay ensures the
valve closes after 45 seconds in case of
deliberate abuse or if an object is placed in
front of the detection field. Once the object is
removed the valve operation will reset
automatically.
• Option: the automatic duty flush can be
overridden or changed to every 12 hours (see
ADJUSTMENTS).
INSTALLATION
• Tap: supply with cold or mixed water.
• Mixer: Supply with cold water and hot water at
70°C maximum, and balance cold and hot
water pressure ( P < 1 bar). Maximum
pressure: 10 bar. Recommended dynamic
pressure: 1 - 5 bar. Take care not to pinch the
flexibles (fig. J).
• To avoid interference from infrared beams do
not install the electronic mixer or tap opposite
a mirror or bright object. Do not install two
TEMPOMATIC mixers or taps opposite each
other.
Deck-mounted model (fig. A)
• Drill a Ø 34mm hole.
• Mount the mixer/tap body onto the washbasin
and tighten the two screws 2 (fig. A) onto the
fixing flange.
• Ensure a suitable waterproof seal between the
mixer and the work plan appropriate to the
type of installation.
• Connect the solenoid valve(s) and complete the
installation as shown in the CONNECTION
section.
Wall-mounted BINOPTIC model (fig. B)
• Mount the spout on the wall. The distance
between the top of the washbasin and the
detection cell must be at least 150mm.
Drill a Ø 22mm hole.
• Connect the solenoid valve and
complete the installation as shown in the
CONNECTION section.
Wall-mounted, through-the-wall models
• TEMPOMATIC (fig. C): mount the detector
support through the wall approximately 50mm
above the top of the washbasin (drill a hole
Ø 33mm). Mount the spout through the wall
in line with the detector and approximately
100mm above it (drill a hole Ø 22mm).
• BINOPTIC (fig. D): mount the spout through
the wall. The distance between the top of the
washbasin and the detector must be at least
150mm. Drill a hole Ø 35mm for ref. 379MCH,
and Ø 22mm for ref. 379DER.
• Tighten the nut onto the fixing flange.
• Connect the solenoid valve(s) and complete the
installation as shown in the CONNECTION
section.
Recessed BINOPTIC or TEMPOMATIC models
(fig. E)
WALL
• Make a recessing space, minimum size
188 x 162 x 70mm, so that the bottom of
the spout is approximately 200mm above
the washbasin surface.
• Allow a recess for the water supply pipes and
electrical supply to connect to the electronic
box.
• Solder two Ø12mm pipes onto the connectors.
It is possible to connect the water supply to the
top of the box by turning it upside down.
• Cover with a Ø18mm sheath.
• Push the 4 legs of the box slightly towards the
rear. Two holes at the bottom of the stainless
steel casing will allow its eventual attachment
to the bottom.
• Seal the box, the tube and the sheath.
• Seal the inside and lower edge of the box with
mastic to prevent any water leaking into the
wall. Position the silicone seal behind the
stainless steel wall plate to ensure a waterproof
seal between the wall plate and the wall. Leave
a drainage point to allow any residual water to
drain away.