English
Español
Energi Savr Node
Step 5: QS link wiring
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power via circuit breaker before wiring or servicing the
Energi Savr Node QS unit.
Buttons and LEDs on the front of the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
QS system communications uses PELV wiring. Follow all local
and national electrical codes when installing PELV wiring with
mains wiring.
QS Link Wiring
Length
Wire Gauge
Power (terminals 1 and 2):
1 pair 1,0 mm
Less than 153 m
Data (terminals 3 and 4):
1 pair 0,5 mm
and shielded*
Power (terminals 1 and 2):
1 pair 4,0 mm
153 m to 610 m
Data (terminals 3 and 4):
1 pair 0,5 mm
and shielded*
* Alternate Data-only cable: Use approved data link cable (0,5 mm
twisted/shielded) from Belden, model #9461.
A QS system can have up to 100 zones and 100 devices. The
Energi Savr Node QS unit occupies 1 device position and up to
32 zone positions.
See diagram on the right for QS link wiring.
1. Connect terminals 1, 3 and 4 to all Energi Savr Node QS units.
2. Each Energi Savr Node QS unit has its own built in power supply.
3. Terminate the terminal 2 connection (24 V
unit supplies power up to 3 PDUs. Each QS device should receive
power from only one Energi Savr Node QS unit
(see diagram on page 8).
NOTE: To connect extra wallstations, use a separate power
supply (24 V
), and only connect COM, MUX, MUX to the
wallstations connected to the Energi Savr Node QS unit.
4. Wiring may be daisy chained or t-tapped.
Power draw calculations are not needed for wireless inputs or
inputs connected directly to the Energi Savr Node QS units.
Energi Savr Node
QS DALI Installation Guide
TM
English
Français
|
QS DALI
TM
Available from
Lutron in one cable:
2
GRX-CBL-346S
, twisted
2
2
GRX-CBL-46L
, twisted
2
) so that each control
Português
Italiano
Installation Guide
QS Link Wiring:
• 0,5 mm
to 4,0 mm
2
2
• Strip length: 8,0 mm
• Torque: 0,5 N
m
•
1
1
2
3
3
4
1
1
2
Hi Temp
3
3
4
Hi Temp
Test
Test
Power
Power
L
N
0,5 N m
L
N
0,5 N m
2
QS Link Terminal Connections
Each QS link terminal can accept only two 1,0 mm
4,0 mm
wires (i.e. GRX-CBL-46L) will not fit. Connect as shown
2
below using appropriate wire connectors.
Single
0,5 mm
to
2
4,0 mm
2
each
Deutsch
COM
24 V
MUX
MUX
2
QS
4
2
Energi Savr Node
QS
Ethernet
4
QSNE-2DAL-D
Energi Savr Node
QS
TM
230 V~ 50/60 Hz 100 mA
QSNE-2DAL-D
Z096
N1771
230 V~ 50/60 Hz 100 mA
www.lutron.com
www.lutron.com
+44.(0)20.7680.4481
+44.(0)20.7680.4481
8 mm
8 mm
Two 1,0 mm
2
each
4,0 mm
中文
Ethernet
QS
DALI 1 DALI 2
TM
®
V
D E
wires. Two
2
each
2
Lutron
7
|
®