CONSOLE UNIT
Part 4: Components
4.1 Coil
A. The indoor coil shall be made with a blue colored hydrophilic coating on the aluminum fins and packed with internally
grooved copper tubing, to increase the effective heat exchange surface area by 25%.
B. Copper tubing shall have inner micro-grooves to increase effective heat transfer capabilities.
C. Coils shall be pressure tested at 600~650 PSI using helium leak detection.
D. The coil shall be charged with dry nitrogen for shipping at 70~100 PSI.
4.2 Fan Motor
A. The fan motor shall be a sealed DC multiple-speed resin-packed motor
B. The fan motor shall have permanently lubricated bearings.
4.3 Fan Blade
A. The fan blade shall be a noncorrodible axial fan blower.
4.4 Copper Piping
A. The coil shall be connected to a length of insulated annealed copper.
B. The ends of the tubing shall have male flare connections.
4.5 Air Louvers
A. The supply air shall be distributed by horizontal and vertical motorized louvers.
B. Air Louvers shall provide wide angle of operation for both horizontal (120°) and vertical (90° from top to down) airflow
movement to provide room comfort for each corner.
4.6 Display
A. The floor console indoor unit shall have a 4.5 x 1.1-inch backlit temperature display capable of showing set or
room temperatures.
B. The display shall also have colored icons representing set mode.
C. The display can be turned off from the wireless remote control.
4.7 WiFi
A. The floor console indoor unit shall include a WiFi adapter.
4.8 Filter
A. The floor console indoor unit shall have removable air filter.
B. The air filter shall be washable and reusable.
4.9 Control
A. The floor console indoor unit shall ship with a hand-held infrared remote control (Standard Remote Control).
B. The floor console indoor unit shall be compatible with the Standard Remote Control, Simplified Wired Controller and
Programmable Wired Controller
20
31-5000585 Rev. 0