11

Maintenance

For maintenance, be sure to turn off the main power switch.
CAUTION
Do not handle the buttons with wet hands; otherwise an electric shock may be caused.
◆ <Daily maintenance>
Cleaning of air filter
1
If
is displayed on the remote controller, contact to service
on maintenance professional to cleaning the air filter.
2
Clogging of the air filter decreases cooling/heating
efficiency.
3
After cleaning, push
.
display disappears.
◆ <Air filter cleaning method>
1
Take out the air filter.
Push the tabs (Forward direction as shown in the figure) of the air filter, and then pull out it to take out the air filter.
2
Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid water with neutral detergent or water.
• After cleaning with water, dry the air filter sufficiently in a shade place.
3
Mount the air filter.
Attach the filter to the main unit while pushing the tabs
(Forward direction as shown in the figure).
4
Push
.
display disappears.
NOTE
When connecting a return air ducting to the unit, the cleaning method of the air filter differs
according to the construction of duct end. Please ask the constructor for construction of air
duct.
127-EN
1,2
3
Air filter
Main unit
Force
Remove the filter from the
main unit while pushing
down on the tabs.
CAUTION
• Do not start the air conditioner while leaving air filter removed.
• Push the filter reset button. (
indication will be turn off.)

▼ Periodic Maintenance

For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be
cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof treatment, if
necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit at least once
every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and even
compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Access from inspection opening and remove the access panel. Examine the heat exchanger if there
Heat exchanger
is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Access from inspection opening and remove the access panel. Examine the fan if there are any
Fan
waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Access from inspection opening and remove the access panel. Check if there is any clogging or drain
Drain pan
water is polluted.
▼ Maintenance List
Part
Unit
Heat exchanger
Indoor / outdoor
Fan motor
Indoor / outdoor
Filter
Indoor
Fan
Indoor
Air intake / discharge
Indoor / outdoor
grilles
Drain pan
Indoor
Ceiling panel, louvres
Indoor
Exterior
Outdoor
– 64 –
Inspection method
Check (visual / auditory)
Maintenance
Wash the heat exchanger when it is
Dust / dirt clogging, scratches
clogged.
Take appropriate measures when
Sound
abnormal sound is generated.
• Wash the filter with water when it is
contaminated.
Dust / dirt, breakage
• Replace it when it is damaged.
• Vibration, balance
• Replace the fan when vibration or
balance is terrible.
• Dust / dirt, appearance
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
Dust / dirt, scratches
deformed or damaged.
Dust / dirt clogging, drain
Clean the drain pan and check the
contamination
downward slope for smooth drainage.
Wash them when they are contaminated
Dust / dirt, scratches
or apply repair coating.
• Rust, peeling of insulator
Apply repair coating.
• Peeling / lift of coat