Water discharge

SPRAY sector exhaust system diagram
1- Water entry via ramp
2- Water misting using nozzles
3- Condensation and water fall downwards
4- Collection of water in the recovery tank
5- Water replenishment in the plant (adiabatic panels)
The system includes a water discharge system used by the adiabatic panels.
The water is collected in a modular basin in which the adiabatic panels are inserted.
4 discharge points are provided (2 per side) to allow rapid emptying of the basin. (threaded connections 1 "¼)
The water coming from the adiabatic panels will be completely discharged and not reused.
ADIABATIC PANEL sector exhaust system diagram
6- Water inlet through distribution pipe
7- Water drop through holes in the distribution pipe
8- Wetting adiabatic panels and falling water downwards
9- Water collection along drainage channel
10- Complete water drainage of the system
Water
coming
from
adiabatic
panels
Water to
lose
Water
coming
from the
exchangers
Water
collected in
the tank
19