7435 NOTICE N°136
6/02/08
UK
1
CAUTION
Plus is a pump for lifting condensation water
from an air conditioning system, a condensation boiler or from
SANICONDENS
®
refrigeration units. Include a neutralisation device if necessary
(see the manufacturer's instructions for your boiler).
The pump starts automatically and has a high level of
performance, safety and reliability provided that all the
installation and maintenance instructions described in this
notice are strictly followed.
Please take particular note of the information marked by :
"
" Indication that a risk of electrical origin exists,
"
" Instructions for use only by qualified professionals.
OPERATING PRINCIPLE
Plus contains a pump. The tank of the
SANICONDENS
Plus is fitted with a float which controls the
®
operation of the motor. When the condensates enter the tank,
SANICONDENS
®
the pump starts up.
LIST OF DOCUMENTS PROVIDED: see fig.2
2
DIMENSIONS: see fig.3
3
4
SANICONDENS
Plus AREA OF APPLICATION AND
®
TECHNICAL DATA
Air conditioning systems, boilers,
Application
Type
Max. vertical pumping
Maximum flow rate (litres / hour)
Flow rate at 4 m
Min. pH
Voltage
Frequency
Power rating
Current consumption
Electrical class
Protection index
Sound level
Average utilisation temperature
Maximum allowable temperature
Net weight
Dimensions
Tank volume
Supply cable
Discharge hose
Alarm cable (3 core)
Wall fastening
All applications other than those described in this notice are
CAUTION:
prohibited.
PERFORMANCE CURVES: see fig.5
5
6
VERTICAL PUMPING/HORIZONTAL PUMPING:
see fig.6
14:39
Page 6
NS01-CD10
refrigeration units
4,5 m
342
156
2,5
220-240 V
50 Hz
60 W
0,52 A
IP20
I
< 45 dBA
35°
80°
S3 15% (90s ON, 510s OFF)
2000 g
277x160x146 mm
2,1 litre
2 m
6 m
2 m
Yes
7
INSTALLATION
Plus has wall fixings.
The unit should be easy to access for testing and
SANICONDENS
®
maintenance.
The unit must be installed level. Adjust the installation using a
spirit level before fixing the unit.
Make sure that the equipment is protected from damp while
installing it.
7a
CONNECTION AT THE COVER INLET
The unit has 4 inlets 28 mm in diameter (2 on each side - see
fig.
). To connect the water to be drained off, connect
7a
1
the water inlet to one of the inlets and close off any unused
inlets with the plugs
. If necessary, use the rubber adaptator
19, 32, 40 mm (see fig.
D
7a
X
7b
CONNECTING TO THE DISCHARGE PIPE
The SANICONDENS
Plus discharge pipe must be connected
to the flexible hose
(supplied : length 6 m). This hose should
®
be used to form the vertical section of the discharge pipe.
A
• Place the flexible hose onto the non-return valve of the
Plus (see diagram
• Position the flexible hose in the most vertical position
SANICONDENS
®
possible to avoid it kinking.
• It is advisable to make a smooth bend to avoid the hose
kinking.
• The hose has a diameter of less than 8 mm and can be
connected to a PVC hose of larger diameter by a plastic
reducing connection on the horizontal section of the
discharge hose, or connected to your drain by a plastic
reducing connection
. In UK fittings such as Speedfit
from John Guest are available -part numbers
Y
PEM202215W used with PEM06150W to connect to 22mm
pipework.
The SANICONDENS
Plus is fitted with a non-return valve
to prevent re-activation.
®
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7c
ELECTRICAL CONNECTION
The electrical installation should be carried by a qualified person.
The unit should be connected to a fully earthed electrical
supply. All wiring must conform to BS7671, 1992 requirements
for electrical installations. The SANICONDENS
a 220/240V single phase AC 50 Hz supply (UK specification).
Do not connect SANICONDENS
and socket. It must be wired into a fused, unswitched, fixed
wiring connector fitted with a 5 amp fuse. SANICONDENS
Plus has an Earth wire. The wires in the mains lead are
coloured in accordance with the following code:
Brown – Live
Blue – Neutral
Ensure the electricity is turned OFF at the main
switch board before wiring to connector.
Warning:
All work on cable, pressure chamber and motor should only
be carried out by a qualified Saniflo servicing agent, as
special tools are required.
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7d
ALARM
Plus is fitted with a detection system
that can trigger an alarm if the water level rises too high
®
SANICONDENS
(audible or visual alarm, 1.5V to 230V), see diagram
. Brown wire: shared wire
1
. Black wire: normally off
2
. Blue wire: normally on
3
To fit the alarm, connect the blue and brown wires
of the alarm to the respective terminals on the
SANICONDENS
®
Plus.
).
2
) .
7b
Plus requires
®
Plus to a conventional plug
®
®
Green/Yellow – Earth
:
7d