Observe local regulations concerning limits for manual lifting and handling.
1.
Note the weight of the product stated on the pump and motor nameplates.
2.
Follow one of these procedures according to the weight of the product and local regulations.
a. If manual lifting is allowed, grip the pump by the outlet chamber or attach lifting wires to the wire hooks.
b. If manual lifting is not allowed, attach lifting wires to the wire hooks and use appropriate lifting equipment. Remove the lifting wires
before the product is lowered below ground level.
Related information
5.1 Handling the product
5.2 Storing the product
8. Taking the product out of operation
3.2.2 Cable termination kit
We recommend that you join the submersible drop cable and the motor cable by means of a Grundfos cable termination kit, type KM.
Cable termination kit, type KM
2
Cross-sectional area [mm
]
1.5 to 6.0
> 6.0
3.2.3 Connecting the pipes
WARNING
Pressurised system
Death or serious personal injury
‐
Design the system for the maximum pump pressure plus 10 % to avoid pipe burst.
We recommend that you install a pressure relief valve designed for the maximum pump pressure.
Minimum torque for fitting the first riser pipe section to the pump is 55 Nm.
Product number
96021473