Bosch AVIOTEC IP starlight 8000 Guía De Instalación Rápida página 22

Ocultar thumbs Ver también para AVIOTEC IP starlight 8000:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 24
22
en | Safety instructions
Notice!
Minimum Illumination required.
i
To ensure the proper functioning of the video-based fire
detection algorithm, a minimal illumination of 2 lx is required. If
the illumination is less than 2 lx, an additional IR illumination is
required.
Notice!
i
No detection of moving fire.
Moving fires will not be detected by the video-based fire
detection.
Notice!
i
No existing standards.
There are no existing EN standards concerning the video-based
fire detection.
Notice!
i
Avoid obstructions in the field of view!
Covered fires cannot be detected correctly. An unobstructed
view of the detection area is necessary.
Notice!
i
Optimized smoke detection.
The video-based fire detection algorithm is optimized for smoke
of smoldering fires.
Notice!
i
Calm wind conditions only.
Strong air currents can cause false alarms by raising dust or
debris similar in appearance to fire and smoke.
Notice!
i
Avoid image regions with continuous upward motion.
Continuous upward motion might lead to false alarms.
2021.07 | 9.0 | F.01U.317.838
AVIOTEC IP starlight 8000
Bosch Sicherheitssysteme GmbH
Tabla de contenido
loading

Este manual también es adecuado para:

Fcs‑8000‑vfd‑b

Tabla de contenido