Features

Temperature Control

This unit must be controlled by a Class 2 remote control
wall mounted heating and cooling thermostat. Refer to
About Your Heat Pump (AZ95H Only)
Heat pumps can save money by removing heat from the
outside air—even when the outside temperature is below
freezing—and releasing that heat indoors.
To get the best energy performance from your heat
pump, don't change the room thermostat by more than
one degree at one time. Raising the heat setting 2–3
degrees may cause the Zoneline to use its electric
heating elements in order to reach the new temperature
setting quickly.
The electric heating elements use more electricity than
heat pumps and cost more to operate.
Do Not Operate the Air Conditioner (cool mode) in Freezing Outdoor Conditions
Air conditioners are not designed for use when freezing outdoor conditions exist. They must not
be used in freezing outdoor conditions.

Quick Heat Recovery

Activates each time the thermostat is switched from OFF or COOL mode to HEAT mode. Electric heaters are
energized until the thermostat set point is reached. On heat pump models, the heat pump operation will resume at
the next call for heat.
6
the operating instructions of the thermostat being used
on how to control the unit.
There is a 3-minute minimum compressor run time at
any setting to prevent short cycling.
The fans start before the compressor and stop after the
compressor cycles off.
When the outdoor temperature is determined to be too
cold, heat is provided by the electric heater instead of by
the heat pump.
When the outdoor temperature is lower than 35°F,
cooling operation is locked out to prevent damage to the
compressor. Operation will resume when the outdoor
temperature rises above 40°F.