Connecting Several Temperature Probes - MYPV AC-THOR 9s Instrucciones De Montaje

Ocultar thumbs Ver también para AC-THOR 9s:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

When installing several devices side by side, a minimum distance of 10cm must be
observed!
Then the electrical connections can be made.
Do not immerse my-PV temperature sensor(s) directly in water. Use a thermowell!
TIP: For mains leads, use a cable duct with a depth of 60 mm.
The necessary cut-out measures 130 x 60 mm.

Connecting several temperature probes

Up to four digital temperature probes (three-core, bus system) can be connected to the
AC•THOR 9s. The terminal positions for the three cores are shown in the following illustration.
TIP: If more than one probe is used, the cores can also be connected externally
in parallel!
Temperature probe
clamping points
Terminal clamps
AC•THOR
®
9s Montageanleitung / Assembly Instructions, Version 210615
7cm
7cm
10cm
10cm
16
Tabla de contenido
loading

Tabla de contenido