INSTALLATION INSTRUCTIONS
C-AR-A-AL Series
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1.
DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l'alimentation
avant l'installation.
2.
This luminaire must be installed in accordance with the
NEC or your local electrical code. If you are not familiar
with these codes and requirements, consult a qualified
electrician.
Ce produit doit être installé conformément à NEC ou votre
code électrique local. Si vous n'êtes pas familier avec ces
codes et ces exigences, veuillez contacter un électricien
qualifié.
3.
Suitable for Wet Locations.
Adspte pour les Endroits Mouiles.
4.
Min. 75C supply conductors.
Les fils d'alimentation 75C min.
5.
Class 1 wiring only.
Cablage de classe 1 uniquement.
6.
SUITABLE FOR OPERATION IN AMBIENT NOT
EXCEEDING =50°C.
PEUT ETRE UTILISE A UNE TEMPERATURE
AMBIANTE N'EXCEDANT PAS 50°C.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
NEMA
PHOTOCONTROL RECEPTACLE
®
NOTE: Fixture will not operate without the supplied shorting cap or a
3-pin or 7-pin NEMA
photocontrol installed in NEMA
®
receptacle.
NOTE: Never install fixture without a shorting cap or NEMA
photocontrol installed into photocontrol receptacle.
following:
photocontrol
®
®
http://lighting.cree.com/warranty
Document
LPN00851X0001A0_A
Created By:
TMT
NOTE: Dimming capabilities are accessible through the NEMA
7-pin receptacle when used with a NEMA
dimming capabilities. If dimming is accomplaished using 7-pin NEMA
photocontrol, make sure dimming cord leads are capped off.
1.
Insert the pins on the supplied shorting cap or customer supplied
photocontrol into the slots on the photocontrol receptacle on top of
the fixture,
NOTE: One pin is wider than the other two pins and must be
inserted into the widest slot. Do NOT force pins into receptacle if
pins are not properly oriented with slots.
2.
Once pins are inserted into receptacle, rotate photocontrol or
shorting cap approximately 1/8 turn clockwise to lock it in place.
SLIP FITTER MOUNTING
(Requires use of C-AR-A-ALSF Accessory)
NOTE: Maximum tilt angle for the fixture is 45°. Fixture is not to be
used as an uplight.
1.
Pass (2) fixture cords through top hole in lower fitter and out
through open end of lower fitter. See Figure 1.
2.
While gently pulling on the ends of the (2) cords, bring the two
halves of fitter together and partially tighten supplied 10 mm bolt
with lockwasher and flat washer on bolt to hold the two halves of
fitter together. Make sure the lockwasher is positioned closest to
the head of the bolt. Do not fully tighten bolt at this time.
3.
Route supply leads up through 2-3/8" (60 mm) O.D. heavy wall
pipe or tenon that the fixture will be mounted on.
4.
Splice supply leads to fixture leads per the Electrical Connections
section.
NOTE: Strain relief is required for electrical connections at
mounting heights of 25' (7.6 m) and above. Knot the supply wires
from the pole with the fixture cord inside the pole to provide strain
relief.
5.
Route cord and splices into open end of tenon while slipping lower
fitter over 2-3/8" (60 mm) O.D. heavy wall pipe or tenon, making
sure not to pinch any leads.
6.
Aim the fixture in the proper direction and hand tighten all four
Allen head set screws against the outer wall of the tenon. Once
all four screws are hand tightened, secure them by gradually
tightening in an "x" pattern to 140 in-lbs (16 N•m).
7.
Tilt the fixture to the desired angle and tighten the 10mm
adjustment bolt between the two halves of the fitter to
32.5 ft-lbs. (44 N•m) to lock the slip fitter in place.
FIGURE 1
Fixture
|
866.924.3645
Date:
03-03-2021
®
7-pin photocontrol with
®
45° MAX
Adjusting Bolt
(4) Set Screws
Lower Fitter
Wire
Tenon
®