Trouble shooting

Introduction
Error signalling
LED displays
Software ≥2 .0
Error messages
on the remote
control's LCD panel
PC-Tool
Reset the unit after
a restart
32
This section shows how to acknowledge and understand possible operation errors .
Errors are indicated by an LED located under the filter reset button . If the LED slowly flashes
orange, it means you need to replace the air filters . See page 29 .
If this LED is red it indicates an operating error . The red LED can indicate three different errors:
LED Red
Description
Flashing slowly
• Error on the bypass damper
• Error on the internal temperature sensor T3/T4
Flashing rapidly
• Error on the fan
• Supply temperature is <+5°C
• External fire alarm is activated
• One of the internal temperature sensors is measuring >70°C
Lights constantly
• T1/T2 Temperature sensor is defective
If the LED flashes RED then there is an operating error . The length of the flash corresponds to
an error code with corresponding digits in the left column of the table below, followed by a 5
second break .
Number of
Error number
flashes
Control panel
1
E1
2
E2
3
E3
4
E4
5
E5
6
E6
7
E7
8
E8
9
E9
10
E10
11
E11
12
E12
13
E13
14
E14
15
E15
Errors are displayed on the HRC3 remote control with an "E" + a number . The error can then
be looked up in the troubleshooting overview and in the control panel's manual for rectifying
errors .
Operating warnings and errors are logged in the controller's memory . Connect a computer
with PC-Tool installed via USB to output detailed information from the logfile .
A restart of the unit (disconnect/connect 230V) will reset the controller and start the unit up
in standard operating mode .
The controller will subsequently check for any errors . This can take up to 15 minutes .
Error
Exhaust fan
Supply fan
Bypass damper
Outside air temperature sensor (T1)
Supply air temperature sensor (T2)
Extracted air temperature sensor (T3)
Exhaust air temperature sensor (T4)
Indoor air temperature sensor (T5)
Humidity sensor, RH% (Accessory)
Outside temperature < -13 °C
Supply air temperature < +5 °C
Fire alarm, one or more of the internal sensors are measur-
ing a temperature above 70 °C .
Communication error / poor signal
Fire alarm, thermostat in the duct system (Accessory)
High water level