Preventative maintenance

Introduction
Preventative maintenance is necessary at regular intervals if the unit is to function efficiently
and optimally, in order to avoid unintended operation stoppages and to ensure the expected
lifetime of minimum 10 years .
It is important to notice, that intervals between filter maintenance can vary depending on
the specific environment, and that moving parts are wearing parts, that needs replacements
when worn down dependent on the specific environment .
The factory warranty only applies if it can be documented that regular preventative main-
tenance has been carried out as prescribed . The documentation can consist of a written log
including a company stamp or equivalent .
Interval summary
At minimum, maintenance must be carried out as shown here:
Interval
6 month
1 year
2 years
Injury by electric shock and risk of damage to the device
Warning
CAUTION
• A biannual inspection every other year is to be performed by trained professionals only .
• Turn off the unit while carrying out inspections of the unit's internal parts .
Caution
• If the power supply cable is damaged, this must be replaced by trained professionals .
Filters (6 month)
After 6 months a filter alarm is triggered . A buzzer will sound and the LED of the "!"-button
will light orange . If the LED lights RED, please see the section: Troubleshooting on page 32 .
Inspect the filters . Even if only one of the filters is dirty, we recommend that you change both
filters so as not to create an imbalance in the air flow through the unit .
After changing the filters, the filter alarm must be reset . See page 28 .
The timer period for the filter alarm can be changed via remote control or PC-Tool .
Filters (1 year)
Change the filters at least once each year regardless of whether they are dirty or an alarm has
been triggered . After changing the filters, the alarm must be reset . See page 28 .

Service Guide

Task
Check filters, Replace if
required
Replace filters
Inspect and clean fans
Inspect and clean electrical
preheater if installed
Clean internal air path
Inspect condensate water
discharge hose
To be carried out by
User
User
Trained professsionals
Trained professsionals
Trained professsionals
Trained professsionals