Operation
9. 3-Phase Load Inquiry
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x00DD
221
R-Phase of load
0x00FC
252
S-Phase of load
0x00FD
253
T-Phase of load
0x00FE
254
The whole load
10. 3-Phase Bypass Info
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x011A
282
R-Voltage of bypass
0x011B
283
S-Voltage of bypass
0x011C
284
T-Voltage of bypass
0x011D
285
R-Current of bypass
0x011E
286
S-Current of bypass
0x011F
287
T-Current of bypass
0x0123
291
Bypass frequency
11. Output Power Factor Inquiry
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x030F
783
R-Output power factor
0x0310
784
S-Output power factor
0x0311
785
T-Output power factor
12. Load Level Inquiry
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x0312
786
R-Watt percent
0x0313
787
S-Watt percent
0x0314
788
T-Watt percent
0x0315
789
R-VA percent
0x0316
790
S-VA percent
0x0317
791
T-VA percent
13. UPS Working Mode
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x00D0
208
UPS Mode inquiry
6
Unit
%
%
%
%
Unit
0.1V
0.1V
0.1V
0.1A
0.1A
0.1A
0.1 Hz
Unit
0.001
0.001
0.001
Unit
%
%
%
%
%
%
Unit
See Appendix 2