GeoSmart NETZERO BW Manual Instalador página 13

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

A)
B)
DO17
C)
DO16
DO6
D)
DO16
DO6
Integrated components
The following source circuit components are included within the heat pump.
Variable speed and high efficiency outlet pump (energy class A).
Expansion vessel with a capacity of 8 litres, with pre-adjusted pressure of 0,75 bar (pressure gauge) (75 kPa).
Safety valve loaded at 3 bar (pressure gauge) (300 kPa).
Drain valve.
Installation instructions
Follow the instructions below to wire the source circuit.
Install the necessary components to carry out the filling/discharge of the return pipe.
Install a particulate filter in the return pipe with a mesh size no greater than 1 mm. It is recommended to install shut off valves
immediately before and after the filter to make it easier to clean or replace.
Check that the volume of the expansion vessel integrated in the heat pump is capable of absorbing any overpressures from
the circuit. If this volume is not enough, install a supplementary external expansion vessel.
If necessary, adjust the pressure of the expansion vessel integrated in the heat pump to guarantee that the circuit remains
pressurised at all points.
Source circuit pressure should be between 0,7 and 2 bar (pressure gauge) (70 and 200 kPa).
GEOSMART ENERGY
4
3
AO6
M
4
3
AO3
4
3
AO3
T
AI12
4
3
DO17
DO16
Figure 3.1. Source circuit connection options.
4
4
3
3
13
Installer manual NETZERO