Error Messages - Pfannenberg DTS Serie Manual De Instrucciones

Ocultar thumbs Ver también para DTS Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 242
ENG
7.1.1

Error messages

The error numbers are not displayed in units with Standard Controllers. Using the ECoolPLANT software, it is possible to read
out the error numbers on the computer.
NOTE
Flashing of the red LED light on the controller card is not a fault indication or error message.
The red LED light indicates that the cooling unit is carrying voltage.
Error no.
Fault/unit behavior
Er00
LED:
Compressor:
Evaporator fan (internal):
Condenser fan (external):
Fault signal contact::
Er01
LED:
Compressor:
Evaporator fan (internal):
Condenser fan (external):
Fault signal contact::
Er04
LED:
Compressor:
Evaporator fan (internal):
Condenser fan (external):
Fault signal contact::
Er05
LED:
Compressor:
Evaporator fan (internal):
Condenser fan (external):
Fault signal contact::
Er07
LED:
Compressor:
Evaporator fan (internal):
Condenser fan (external):
Fault signal contact::
Tab. 10: Possible error messages
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 400 V, 2~ | 086100003e
Possible causes
flashes
Door contact:
The door contact circuit is
OFF
interrupted.
OFF
OFF
closed
flashes
Pressostat tripped:
Too high pressure in the
OFF
refrigeration circuit.
ON
The cooling unit cannot
dissipate the heat from the
OFF
refrigeration circuit.
Open
flashes
Phase sequence/phase
failure:
OFF
Failure of at least one
OFF
phase or phase sequence is
wrong (only in three-phase
OFF
units with cam
compressors).
Open
flashes
Sensor 1 (TS1) defective.
ON
ON
ON
Open
flashes
Sensor 1 Maximum:
Maximum value of the
ON
switch cabinet temperature
"
¯" (
ON
exceeded.
ON
The cooling unit cannot cool
Open
the air in the switch cabinet
sufficiently.
Remedial measures
Close the door.
Connect the door contact
switch.
Bridge the door contact.
Check wiring.
Let the unit cool down.
Clean the fins of the heat
exchanger
(internal/external).
Check the function of the
condenser fan (external).
Check field of rotation -
(right-hand field of rotation
is mandatory).
All phases must carry rated
voltage.
According to the unit type,
replace sensor 1
(permanently soldered on
the controller card) or the
complete controller card.
Check settings of the
cooling unit.
Clean the fins of the heat
y)
exchanger
(internal/external).
Check the function of the
evaporator fan (internal).
Check the refrigeration
circuit for spilled refrigerant
or leakage.
Install a cooling unit with a
higher cooling capacity if
necessary.
52/60