Setting:
1 Open parameter r12 and stop the regulation
2 Select electric connection based on the drawings on page 2
3 Open parameter o61 and set the electric connection number in it
4 Now select one of the preset settings from the table on the right-
hand side
5 Open parameter o62 and set the number for the array of presettings
6 Open parameter r12 and start the regulation
7 Go through the survey of factory settings. Make any necessary
changes in the respective parameters.
8 For network. Set the address in o03 and then install on the system
unit by scanning, or for Lon via setting o04.
Function
Normal operation
Temperature (set point)
Thermostat
Differential
Max. limitation of setpoint setting
Min. limitation of setpoint setting
Adjustment of temperature indication
Temperature unit (°C/°F)
Correction of the signal from Sair
Manual service, stop regulation, start regulation (-1, 0, 1)
Displacement of reference during night operation
Activation of reference displacement r40
Value of reference displacement (activate via r39 or DI)
Alarm
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit
Low alarm limit
Alarm delay DI1
Alarm delay DI2
Alarm limit for condenser temperature alarm
Limit for condenser block alarm and comp. stop
Delay for condenser block alarm
Difference for clearing condenser alarms
Compressor
Min. ON-time
Min. OFF-time
Time delay for cut-in of comp.2
Defrost
Defrost method (none/EL/GAS)
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cut-in of defrost at start-up
Drip off time
Delay for fan start after defrost
Fan start temperature
Fan cut-in during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
Defrost sensor (0=time, 1=S5, 2=Sair)
Pump down delay
Max. aggregate refrigeration time between two defrosts
Defrost on demand - S5 temperature's permitted variation during frost build-up. On
central plant choose 20 K (=off )
Max. duration of -d- in display
Fan
Fan stop at cut-out compressor
Delay of fan stop
Fan stop temperature (S5)
© Danfoss | DCS (vt) | 2021.03
ENGLISH
Parameters
Table for Quick settings
Preset setting – via o62
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Alarm limit high (A13)
Alarm limit low (A14)
Grey marked settings will be changed by the Quick setting function.
See table above.
Variant of AK-CC
Codes
1
2
3
4
---
***
r01
***
r02
***
r03
r04
r05
r09
r12
r13
r39
r40
A03
***
A04
A12
***
A13
***
A14
A27
A28
A37
A54
A55
A78
c01
c02
c05
d01
d02
d03
d04
d05
d06
d07
d08
d09
d10
d16
d18
d19
d40
F01
F02
F04
MT (cooling)
LT (frost)
cabinet
cabinet
1
4.0 °C
-24.0 °C
6.0 °C
-22.0 °C
2.0 °C
-26.0 °C
10.0 °C
-15.0 °C
-5.0 °C
-30.0 °C
Min.-
Max.-
Factory
5
value
value
setting
-50.0 °C
50.0 °C
2.0 °C
0.1 K
20.0K
2.0 K
-49.0 °C
50 °C
50.0 °C
-50.0 °C
49.0 °C
-50.0 °C
-20.0 K
20.0 K
0.0 K
°C
°F
°C
-10.0 K
10.0 K
0.0 K
-1
1
0
-20.0 K
20.0 K
0.0 K
OFF
ON
OFF
-50.0 K
50.0 K
0.0 K
0 min.
240 min.
30 min.
0 min.
240 min.
60 min.
0 min.
240 min.
90 min.
-50.0 °C
50.0 °C
8.0 °C
-50.0 °C
50.0 °C
-30.0 °C
0 min.
240 min.
30 min.
0 min.
240 min.
30 min.
20.0 °C
120.0 °C
60.0 °C
20.0 °C
140.0 °C
70.0 °C
0 min.
30 min.
0 min.
1.0 K
30.0 K
10.0 K
0 min.
30 min.
0 min.
0 min.
30 min.
0 min.
0 sec
900 sec
5 sec
none
GAS
none
0.0 °C
25.0 °C
6.0 °C
0 hours 240 hours 8 hours
0 min.
180 min.
45 min.
0 min.
240 min.
0 min.
0 min.
60 min.
0 min.
0 min.
60 min.
0 min.
-15.0 °C
0.0 °C
-5.0 °C
0
2
1
0
2
0
0 min.
60 min.
0 min.
0 hours
48 hours
0 hours
0.0 K
20.0 K
20.0 K
5 min.
240 min.
30 min.
no
yes
no
0 min.
30 min.
0 min.
-50.0 °C
50.0 °C
50.0 °C
AN33481406482302-000201 | 3
2
SW = 1.0x
Actual
setting