MAINTENANCE
1. Perform visual, electrical, and mechanical inspections on a regular basis.
The environment and frequency of use should determine this. However, it
is recommended that checks be made at least once a year. We
recommend an Electrical Preventive Maintenance Program as described in
the National Fire Protection Association Bulletin NFPA No. 70B:
Recommended Practice For Electrical Equipment Maintenance
(www.nfpa.org).
2. The lens should be cleaned periodically to ensure continued lighting
performance. To clean, wipe the lens with a clean, damp cloth. If this is
not sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or
Duco #7. Do not use an abrasive, strong alkaline, or acid cleaner.
Damage may result.
3. Visually check for undue heating evidenced by discoloration of wires or
other components, damaged parts, or leakage evidenced by water or
corrosion in the interior. Replace all worn, damaged, or malfunctioning
components, and clean gasket seals before putting the luminaire back into
service.
4. Electrically check to make sure that all connections are clean and tight.
5. Mechanically check that all parts are properly assembled.
6. To prevent heat build-up, remove dust from the fins on the LED housing,
using a soft brush or air pressure.
REPLACEMENT PARTS
Cooper Crouse-Hinds Vaporgard Series Luminaires are designed to provide
years of reliable lighting performance. However, should the need for
replacement parts arise, they are available through your authorized Cooper
Crouse-Hinds distributor. Assistance may also be obtained through your local
Cooper Crouse-Hinds representative.
Cooper Crouse-Hinds Sales Service Department, P.O. Box 4999, Syracuse,
New York 13221, Phone (315) 477-7000.
LED MODULE REPLACEMENT INSTRUCTIONS
1. Turn off all electrical power to the luminaire before opening.
2. Loosen captive cover screws, open luminaire, and leave hanging on the
support hinge.
3. Disconnect supply wire from the luminaire and remove LED housing.
4. Remove any gasket material or debris from the bottom of the adapter
cover.
5. Install new LED housing:
a.
Hang the LED housing on the hinge of the adapter cover (see
Figure 2).
b.
Connect cover ground lead with fork terminal to ground screw
on LED housing. Tighten ground screw (see Figure 3).
c.
Connect supply wires to the LED driver input leads per the
appropriate wiring diagram, using methods that comply with all
applicable codes. Tighten all electrical connections.
d.
Close LED housing onto adapter cover, ensuring that wires are
not caught between the cover and the LED housing. Tighten
three (3) cover screws using a 3/16 inch (4.7 mm) hex allen
wrench (see Figure 4). Torque to 75 lb.-in. (8.5 N-m).
LED DRIVER REPLACEMENT INSTRUCTIONS
1. Turn off all electrical power to the luminaire before opening.
2. Loosen captive cover screws, open luminaire, and leave hanging on the
support hinge.
3. Disconnect supply wire from the luminaire and remove LED housing.
4. Remove any gasket material or debris from the bottom of the adapter
cover.
5. Install new LED driver:
a.
Disconnect driver output leads. Remove and set aside screws
holding the LED driver to the LED housing. Remove driver (and
terminal block bracket, for NV2L units).
b.
Place new driver into housing, orienting it so that the output
wires are next to the wires for the LEDs. Align mounting feet
with holes in housing.
c.
For NV2L units, place terminal block over mounting feet on driver.
d.
Install mounting screws removed from the old driver. For NV2L
units, install mounting screws through terminal block bracket and
driver mounting feet. Tighten mounting screws. Strip LED lead
wires to approximately 1/2 inch (12mm).
e.
Connect driver output wires to LEDs per wiring diagrams.
f.
For DC drivers, cap all unused leads.
6. Reinstall LED housing:
a.
Hang the LED housing on the hinge of the adapter cover (see
Figure 2).
b.
Connect cover ground lead with fork terminal to ground screw on
LED housing. Tighten ground screw (see Figure 3).
c.
Connect supply wires to the LED driver input leads per the
appropriate wiring diagram, using methods that comply with all
applicable local codes. Tighten all electrical connections.
d.
Close the LED housing on the adapter cover, ensuring that wires
are not caught between the cover and the LED housing. Tighten
three (3) cover screws using a 3/16 inch (4.7 mm) hex allen
wrench (see Figure 4). Torque to 75 lb.-in. (8.5 N-m).
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof
are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.