One-Touch™ Test Mode
To speed up installation and testing, One-Touch™ testing is provided which allows the inputs and outputs
functionality to be tested at the controller. There are two test modes:
View mode is for use on a configured system.
Active mode is for use during system configuration to enable a system to be walk tested by a single
person. This is achieved by use of latching LED status which indicate the first change in input condition.
Test
Normal
Operation
One-
Hold down the One-
Touch™
Touch™ button for less
View Mode
than 2 seconds.
Note that View mode
will automatically time
out after 2 minutes.
One-
CAUTION
Touch™
Any output relays that should not be triggered must be disconnected before entering Active
Active
mode.
Mode
Hold down the One-
Touch™ button for 2 to
4 seconds.
Trigger each input
sensor in turn and
ensure that the LEDs
indicate the correct
state.
Note
The controller will
operate unconfigured
and no system
communications will
occur.
Hold down the One-
Leave Test
Touch™ button for less
Mode
than 2 seconds.
Active mode will
automatically time out
after 1 hour.
17475v3.0
Action
Both off
Green on
Red on
Both on
Both off
Green on
Red on
Both on
Observation
The green system status LED flashes.
Red and green input status LEDs off.
Green output status LED is off.
The green system status LED flashes at twice the
normal rate.
On an unconfigured system, all red LEDs will
flash briefly three times and test mode is exited.
On a configured system, in general a red LED
indicates a tamper state, a green LED indicates an
active state, and no LEDs indicates a non-active
state or unconfigured input.
View mode is intended for a configured system so
further information is given in the helpfile.
Green off - output is normal
Green on - output is active on a configured system.
The green system status LED flashes four times
faster than normal.
The first change in state will be latched, and the
display for that input will not change until test mode
is exited.
2-state
N/A
N/A
input open
input closed
3-state NO
N/A
input open
input open tamper
input closed
Green output LED is on/off for a 5 second cycle
(relays active/inactive)
All status LEDs off, except green system status
LED flashes at normal rate.
English
4-state
input open
input closed
input open tamper
input tamper short
3-state NC
N/A
input closed
input open
input tamper short