FUNCTION SETTINGS (table 3)
The various options described can be selected by means of the function dip-switch (detail 19 of fig.14).
- Bear in mind that to ensure that the control unit "learns" a variation to settings, it must be switched off and on
again; otherwise briefly short-circuit the 2 reset pins of the control unit.
TAB. 3
Function
Input mode
Step/step
Radio Channel ch1
Output mode
Flashing light
Pre-flashing
Re-close
Closing stroke
Closure position
Deceleration
Edge Input
POWER ADJUSTMENT
According to standard EN 12445 each automation must exceed the impact tests measured by means of the specific instrument.
Perform the impact tests and adjust the force levels of ZEN by means of the trimmer (detail 22 Fig. 14).
If this is not sufficient to remain with the values in the graph as specified by the standards, a soft rubber profile should be installed
at the top of the door to dampen impact.
If power adjustment and installation of the rubber profile still does not enable compliance with standards, alternative devices must
be fitted, such as a safety edge on the mobile edge of the door.
64
N.
OFF ON
Desciption
Dip
1
Open - Stop - Close
2
1
Open - Close
2
1
Open
2
Condominium function
1
Open - Close
2
Cut out of opening control
3
Flashing light
4
(lamp.)
3
Pulse 230V
4
3
Courtesy light
4
3
Indicator light
4
Inhibited
5
Enabled
Inhibited
6
Enabled
Inhibited
7
Enabled
Inhibited
8
Enabled
Inhibited
9
Enabled
NC Input
10
balanced Input
During opening, when pushbutton S/S is pressed the door blocks, and closes
when pressed again. During closure, when pushbutton S/S is pressed the door
blocks, and opens when pressed again.
During opening, when pushbutton S/S is pressed the door blocks for a few
seconds and then closes. During closure, when pushbutton S/S is pressed the
door blocks for a few seconds and then opens.
During opening, there is no action when pushbutton S/S is pressed, and when the door
is open the S/S button restarts the pause time. During closure, when pushbutton S/S is
pressed the door blocks for a few seconds and then opens.
During opening, there is no effect when pushbutton S/S is pressed. During the pause,
when pushbutton S/S is pressed the door closes. During closure, when pushbutton S/S is
pressed the door blocks for a few seconds and then opens.
Intermittent flashing light output. When this mode is set, the flashing light function is
enabled by connection of a standard lamp (230V) to terminals 6 and 7.
One second pulse (230V) every opening movement (the beginning of movement)
fig. 15B.
The output (terminals 6 and 7) becomes a "courtesy light" 230V maximum 100W.
Lit during manoeuvres plus a delay of approx. 2 minutes.
This output has the function of indicator light (with different flashes to indicate door status).
Door closed= off; in opening = slow flash; in closing= rapid flash; in pause = 2 flashes
with pause; door blocked with stop button = steady light. After a reset or power failure
the indicator turns off.
The flashing light is powered at the same time as the motor.
The flashing light is powered 5 seconds before each manoeuvre.
After complete opening, the control unit only re-closes with a manual command.
After complete opening, the control unit re-closes after a set pause time.
Function inhibited
power pulse at end of closing Useful for completing manoeuvres on up-and-over doors.
Function inhibited
Adjusting the closure point after self-learning
Deceleration is not performed on the final part of gate travel.
When deceleration is enabled the motor on approach to each end of manoeuvre
cuts to half the previous speed.
Any safety edges connected must have an NC contact (see table 2)
Any safety edges connected must have an NO contact with 8K2 resistance in
parallel (see table 2)
Notes