Input module CPX-4AE-U-I
(continuation)
– Potential connection to FE
– Sensor supply
– Output voltage
– Load capacity
– Fuse
– Behaviour after end of
overload
– Inverse polarity protection
24 V load input
– Inverse voltage resistance
– Electrical isolation
– Between channel and
24 V
SEN
– Between the channels
26
Voltage inputs
High-impedance, capacitive
connection
One connection per sensor, same
supply potential at all connections,
generation from V
DC 24 V ± 25 %
1.4 A (max. permanent current per
module)
Electronic, thermal
(Response current: 1.4 to 4.5 A)
Can be parametrised
(s. description P.BE-CPX-AX...)
Yes
Max. 30 V
Yes (release electrical isolation by
using the internal sensor supply)
No
Festo CPX-AX 1107d English
Current inputs
EL/SEN